PCKN-OIL738
33
6.4.2.3 Guide for option function
(1) Specifying contact arrangement data of output contacts
The table below shows the setting guide table. See the section D-1 of the general operation
manual for the detailed procedure.
Input
Digit
No.
Setting item
0 1
0
Self hold / auto reset upon reset
judgement
Reset
Hold
1
Undervoltage AB-phase
Off
On
2
Undervoltage BC-phase
Off
On
3
Undervoltage CA-phase
Off
On
4
Not used
X
5
Overvoltage AB-phase
Off
On
6
Overvoltage BC-phase
Off
On
7
Overvoltage CA-phase
Off
On
8
Not used
X
9
Not used
X
10
Not used
X
11
Not used
X
12
Not used
X
13
Not used
X
14
Not used
X
15
OR
elemen
t comb
inati
on
Not used
X
0
0
0
0
0 0
0
0
0
ditto.
ditto.
0
Contact arrangement data
0
Conversion from binary number to hexadecimal
Binary
Æ
Hexadecimal
Binary
Æ
Hexadecimal
Binary
Æ
Hexadecimal
0 0 0 0
Æ
0
0 1 1 0
Æ
6
1 1 0 0
Æ
C
0 0 0 1
Æ
1
0 1 1 1
Æ
7
1 1 0 1
Æ
D
0 0 1 0
Æ
2
1 0 0 0
Æ
8
1 1 1 0
Æ
E
0 0 1 1
Æ
3
1 0 0 1
Æ
9
1 1 1 1
Æ
F
0 1 0 0
Æ
4
1 0 1 0
Æ
A
0 1 0 1
Æ
5
1 0 1 1
Æ
B
ditto.
When the product is shipped from the factory, contact arrangement data are set as follows..
Contact
Item
number
Contact
arrangement
data
Setting of the element
Contact
Item
number
Contact
arrangement
data
Setting of the element
X0 800 000E
Undervoltage
X3 830 00E0
Overvoltage
X1 810 000E
Undervoltage
X4 840 00EE
OR of all the elements
X2 820 00E0
Overvoltage
X5 850 00EE
OR of all the elements
*The “Self hold/auto reset” setting are “Reset” (auto reset) for all contacts.