PCKN-OIL738
8
3 Characteristics
Common conditions
(1) Rated frequency: ±1%
(2) Ambient temperature: 20°C±10°C
(3) Aux. supply voltage: Rated voltage±2%
The conditions shown on the left
should be applied unless otherwise
specified.
3.1 Protective elements
Items Conditions
Guaranteed
performance
Undervoltage
element
Operation
value
Overvoltage
element
(Common conditions)
Setting value ±5%
Undervoltage
element
Operation value × 105% or
less
Reset value
Overvoltage
element
(Common conditions)
Operation value × 95% or
more
Undervoltage
element
Rated voltage
Æ
Setting×70%
-
For setting of INST
40ms or less
-
For setting of 0.4s or less
Setting value ± 25ms
-
For setting of 0.5s or more
Setting value ± 5%
Operation
time
Overvoltage
element
0
Æ
Setting×120%
-
For setting of INST
50ms or less
-
For setting of 0.4s or less
Setting value ± 25ms
-
For setting of 0.5s or more
Setting value ± 5%
Undervoltage
element
Setting×70%
Æ
Rated voltage
Reset time
Overvoltage
element
Setting×120%
Æ
0
60ms or less
3.2 Measurement elements
Items
Condition
Guaranteed performance
Real time and max. records
±1%
Fault record
VT primary setting /
VT secondary setting ×165
±1%