II
Restrictions ]
- 24 -
HWE15070
GB
(5) Re-initializing the system
When the settings for the items below have been changed, the system will require re-initialization.
• Dip switch SW2-8 (use or non-use of an external water temperature sensor) (Re-initialization is required only for
the Multiple system.)
• Dip switch SW2-9 (multiple unit control)
• Dip switch SW3-3 (water temperature control method)
• External signal input setting [107] (total number of units in the system)
• Rotary switches (SWU1 and SWU2) (unit address)
Take the following steps to re-initialize the system:
(1) Set the rotary switch SWU3 to "F."
[FFFF] will appear in the LED1.
(2) Press and hold the push switch SWP3 for one second or longer.
• While the system is starting up [9999] will appear on LED1.
• When start-up is complete, a control property [0012] will appear.
• Then, five seconds later, [FFFF] will appear.
(3) Press and hold the push switch SWP3 again for one second or longer.
• While the system is starting up [9999] will appear on LED1.
• When start-up is complete, a control property [0012] will appear.
• Then, five seconds later, [FFFF] will appear.
(4) Set the rotary switch SWU3 back to "0."
(6) Resetting the system (MAIN and SUB circuits)
Take the following steps to reset the system. An error can also be reset by taking the steps below.
Note that the errors on the MAIN unit must be reset through the MAIN circuit, and the errors on the sub unit must be
reset through the SUB circuit.
When an error on the MAIN unit is reset, all sub units will stop.
(1) Set the rotary switch SWU3 to "F."
[FFFF] will appear in the LED1.
(2) Press and hold the push switch SWP3 for one second or longer.
• While the system is starting up [9999] will appear on LED1.
• When start-up is complete, a control property [0012] will appear.
• Then, five seconds later, [FFFF] will appear.
(3) Set the rotary switch SWU3 back to "0."
0000001906.book 24 ページ 2015年11月5日 木曜日 午前11時55分
Содержание CAHV-P500YB-HPB
Страница 1: ......
Страница 7: ...CONTENTS HWE15070 GB ...
Страница 9: ... 2 HWE15070 GB ...
Страница 19: ... 12 HWE15070 GB ...
Страница 37: ... 30 II Restrictions GB HWE15070 ...
Страница 39: ... 32 HWE15070 GB ...
Страница 48: ... 41 HWE15070 GB IV Remote Controller 1 Using the Remote Controller 43 2 Function Settings 48 ...
Страница 49: ... 42 HWE15070 GB ...
Страница 57: ... IV Remote Controller 50 HWE15070 GB ...
Страница 58: ... 51 HWE15070 GB V Electrical Wiring Diagram 1 Electrical Wiring Diagram 53 ...
Страница 59: ... 52 HWE15070 GB ...
Страница 65: ... 58 V Electrical Wiring Diagram GB HWE15070 ...
Страница 66: ... 59 HWE15070 GB VI Refrigerant Circuit 1 Refrigerant Circuit Diagram 61 2 Principal Parts and Functions 62 ...
Страница 67: ... 60 HWE15070 GB ...
Страница 71: ... VI Refrigerant Circuit 64 HWE15070 GB ...
Страница 73: ... 66 HWE15070 GB ...
Страница 111: ... 104 HWE15070 GB ...
Страница 117: ... VIII Test Run Mode 110 HWE15070 GB ...
Страница 119: ... 112 HWE15070 GB ...
Страница 163: ... IX Troubleshooting 156 HWE15070 GB ...
Страница 164: ... 157 HWE15070 GB X Attachments 1 R407C saturation temperature table 159 ...
Страница 165: ... 158 HWE15070 GB ...
Страница 167: ... X Attachments 160 HWE15070 GB ...
Страница 168: ......