E-22
8.4 Control circuit
8.3 Check of the N-pole (4-Pole)
■
Crimp-type terminal size
Use the connection terminals for M3.5. For
the size, refer to the right figure.
(Note)
If the screw is tightened with excessive
torque, the crimp-type terminal and the
screw may be damaged. Tighten the
screw with the specified torque.
Use a screwdriver that is suitable for the
size of cruciform groove.
Size of toolhead : PH2
Passage wiring
7.2 mm max.
M3.5
×
10
Torque: 1.0
±
0.2 N
・
m
The position of N-pole is selectable. Check the label on the rear side of the circuit breaker before connecting.
CAUTION
Since voltage is applied to the terminals
S1 and S2 , do not touch them.
When an UVT is installed, voltage is
applied to DT1 and DT2 of the terminal
block. Do not touch the terminals.When
not using S1 , S2 , DT1, and DT2, do
not remove the caps on them for safety.
■
Fixed type
■
Drawout type
The recommended terminal is shown below.
Ex. 1.25 mm
2
to 2.0 mm
2
wires
N2-M3 (RAP2-3.5)
FN2-M3 (RBP2-3.5)
N2-YS3A
Manufacturer: J.S.T. Mfg. Co.,Ltd.
N-pole: Left
(
Option
)
N-pole: Left
(
Option
)
N-pole: Left
(
Option
)
N-pole: Left
(
Option
)
N-pole: Right
(
Standard
)
N-pole: Right
(
Standard
)
N-pole: Right
(
Standard
)
N-pole: Right
(
Standard
)
Cap
Cap