7. COMMUNICATION THAT DO NOT REQUIRE
THE SEQUENCE PROGRAM
MELSEC-A
7-38
7.2.10 Bus parameter setting (SetValue: Server)
Use the SetValue to set the parameter in the AJ71PB96F/A1SJ71PB96F from the client.
[Parameters required by the client]
•
Variable Identifier
Set the parameter type to be set as shown in the following table.
•
Desired Value
Set the value as shown in the following table.
Vriable Identifier
Current Value
6
Tsl
Slot time 37 to 16383
7
Min Tsdr
Minimum response delay time 11 to 1023
8
Max Tsdr
Maximum response delay time 37 to 1023
9
Tqui
Quiet time 0 to 127
10
Tset
Setup time 0 to 255
11
Ttr
Target token rotation time 256 to 16777215
12
G
Gap update rate 1 to 100
13
In Ring Desired
Not specified by the A1SJ71PB96F
15
Max Retry Limit
Maximum retry count 0 to 7.
[Server (AJ71PB96F/A1SJ71PB96F) answer parameters]
None