MITSUBISHI ELECTRIC 1100B SERIES UPS
1100B SERIES UPS
OWNERS / TECHNICAL MANUAL
Page Number:
6-3
Code
indication
(Note 2)
Status
Message
Meaning
Guidance
Audible
Alarm
External
relay
contact
(Note 1)
UA865
MODULE BATTERY
DEPLETED
A power converter module has
detected battery depleted.
CALL
SERVICE
ENGINEER
Intermittent
sound
Alarm
UA866
MODULE BATTERY
DEPLETED ALARM
A power converter module issues a
warning on eminent battery
depletion.
CALL
SERVICE
ENGINEER
Intermittent
sound
Alarm
UA891
CHG. PROHIBITED
The relay turned on.
-
Intermittent
sound
Alarm
UA892
DISCHG.
PROHIBITED
The relay turned on.
-
Intermittent
sound
Alarm
UF055
CONVERTER
ABNORMAL
Mixed operation (20 seconds)
CALL
SERVICE
ENGINEER
Intermittent
sound
Minor
UF151
BATTERY
VOLTAGE
ABNORMAL
All power converter modules have
detected battery float voltage
abnormal.
CALL
SERVICE
ENGINEER
Intermittent
sound
Minor
UF156
CHG.STOPPED
(BATTERY
OVERTEMP.)
UF157 failure persisted for over
two(2) hours.
CHECK
BATTERY
Intermittent
sound
Battery
abnormal
UF157
BATTERY
OVERTEMPERA
TURE
Detection of overtemperature at the
batteries.
CHECK
BATTERY
Intermittent
sound
Battery
abnormal
UF158
BATTERY LIQUID
LOW
Low level of battery electrolyte
solution.
CHECK
BATTERY
Intermittent
sound
Battery
abnormal
UF161
CHG.STOPPED
(DC VOLT.
ABNORMAL)
UF151 failure is running for over 24
hours.
CALL
SERVICE
ENGINEER
Intermittent
sound
Battery
abnormal
UF162
BATTERY
ABNORMAL
Failure detection based on battery
self-check.
CALL
SERVICE
ENGINEER
Intermittent
sound
Battery
abnormal
UF163
BATTERY
VOLTAGE
ABNORMAL
All converter modules have
detected battery voltage abnormal.
CALL
SERVICE
ENGINEER
Intermittent
sound
Battery
abnormal
UF202
OUTPUT
UNDERVOLTAGE
Output voltage dropped.
CALL
SERVICE
ENGINEER
Intermittent
sound
Minor
UF253
UPS CONTROL
CIRCUIT ERROR
Discrepancy between output voltage
and bypass voltage during bypass
operation.
CALL
SERVICE
ENGINEER
Intermittent
sound
Minor
UF254
UPS CONTROL
CIRCUIT ERROR
Inverter voltage is out of the
specification level during transfer.
CALL
SERVICE
ENGINEER
Intermittent
sound
Minor
UF256
OUTPUT VOLTAGE
ABNORMAL
Output voltage is out of the
specified range.
CALL
SERVICE
ENGINEER
Intermittent
sound
Minor
UF258
LOAD ABNORMAL
Load transfer due to overload for
over 4 times within 5 minutes.
CALL
SERVICE
ENGINEER
Intermittent
sound
Minor
UF301
UPS CONTROL
CIRCUIT ERROR
AD reference has an abnormal
value.
CALL
SERVICE
ENGINEER
Continuous
sound
Major
UF302
UPS CONTROL
CIRCUIT ERROR
Detection of an external interruption
during the software execution.
CALL
SERVICE
ENGINEER
Continuous
sound
Major
UF303
UPS CONTROL
CIRCUIT ERROR
Timer does not reset in the specified
period (WDT settings)
CALL
SERVICE
ENGINEER
Continuous
sound
Major
UF305
UPS CONTROL
CIRCUIT ERROR
Detection of an abnormal clock
speed in the CPU or FPGA.
CALL
SERVICE
ENGINEER
Continuous
sound
Major
UF306
UPS CONTROL
CIRCUIT ERROR
Control power supply voltage is
below the specified level.
CALL
SERVICE
ENGINEER
Continuous
sound
Major
UF320
UPS CONTROL
CIRCUIT ERROR
Cable disconnection in the parallel
interface board during load supply.
CALL
SERVICE
ENGINEER
Intermittent
sound
Minor