MITSUBISHI ELECTRIC 1100B SERIES UPS
1100B SERIES UPS
OWNERS / TECHNICAL MANUAL
Page Number:
1-13
C) Emergency Operation:
Load power supplied by UPS battery.
Figure 3
Single Line Diagram - Emergency Operation
Referring to Figure 3: In the event of an AC input source failure or interruption, the UPS
converter will de-energize and the UPS battery will immediately discharge and supply DC
power to the inverter to maintain continuous AC power to the load. This operation will continue
until:
a) The battery capacity expires and the inverter turns off, or
b) The input power is restored after which the converter will simultaneously power the inverter
and critical load and recharge the batteries.
A fully charged battery will provide power for the specified time at the rated load, or longer, at a
reduced load.
When power is restored after a low battery shutdown, the UPS converter automatically restarts
operation, the charger recharges the batteries and the Inverter is automatically restarted without
operator intervention. The load is automatically assumed by the inverter without operator
intervention.
UPS Module
Power Flow
AC
input
CB
3
CONVERTER
/
CHARGER
Output
52
C
Static Transfer
Switch
52S
72B
MCCB
User
supplied
CB
52RC
INVERTER
Not in Use
BATTERY
External Battery
Bypass
input
MCCB
User
supplied
CB
Содержание 1100B Series
Страница 2: ...Preface ...
Страница 64: ......