MITSUBISHI ELECTRIC 1100B SERIES UPS
1100B SERIES UPS
OWNERS / TECHNICAL MANUAL
Page Number:
3-5
D)
▲External Battery (10kVA, 20kVA 30kVA, 40kVA 50kVA, 60kVA, 70kVA and 80kVA)
Please refer to the following when installing and maintaining the batteries:
1. The customer shall refer to the battery manufacturer's installation manual
for battery installation and maintenance instructions.
2. The maximum permitted fault current from the remote battery supply and
the DC voltage rating of the battery supply over-current protective device is
shown in Table 11.
▲ For other stored energy systems, refer to the supplement.
Table 10
Maximum Permitted Fault Current
UPS Capacity
(kVA)
DC Voltage
Rating (V)
Maximum Fault
Current Permitted (A)
10
288
25,000
20
288
25,000
30
288
25,000
40
288
25,000
50
288
25,000
60
288
25,000
70
288
25,000
80
288
25,000
E) Installing Air Filter
1. Remove front cover
2. Grip the air filter using three ledges
Filter Size: 16W x 4.3H x 0.8D (in)
3. Close the front cover