Javelin I & II Power Supply Operator’s Manual 

Voltage conversion is achieved by Vicor’s family of Zero-Current-Switching (ZCS) DC-DC converters.  These 
are forward converters in which the main switching element switches at zero current.  This patented topology 
has a number of unique attributes: low switching losses, high frequency operation (resulting in reduced size for 
magnetics  and  capacitors),  excellent  line  and  load  regulation,  wide  output  adjustment  range,  low  EMI/RFI 
emission, and high efficiency. 
 
At initial power-up, the Javelin output is disabled to limit the inrush current and to allow the DC bus potential 
to settle out to the correct operating level.  A low-power flyback converter operating with PWM current-mode 
control converts the high voltage DC bus into regulated low voltage to power the internal housekeeping circuits 
and DC cooling fans. 
 
The internal housekeeping Vcc comes up within 1 second after the application of input power.  Once the high 
voltage bus is within operating limits, the AC Power OK signal changes its output to a TTL “1,” indicating the 
input power is OK, and allows the power output to come up 15-30 ms later.  An auxiliary Vcc output of 5 VDC 
capable of sourcing up to 300mA is provided for peripheral use. 
 
An output Inhibit/Enable function is provided by using an optocoupler to control Vicor’s DC-DC converters.  If 
the Inhibit control pin is pulled low and the Enable pin is high or open, the optocoupler will turn on and disable 
the output.  The delay for an output to come up when measured from release of the Enable pin is 5-10 ms. 

Power

Output

Line Filter

Rectifier

Soft Start

Circuit

Boost Converter

Output

PFC Control

Customer

Interface

I/E Control

Fan

Housekeeping

Power

Input

Current
Sample

Waveform Sample

Inhibit/Enable Control

Inhibit/Enable

Figure 1. Javelin Architecture 

Interface Connections 

Input Power Terminal (J1)

 

 

Input AC (and DC) Power is applied to connector J1 using a 3W3 power 
connector. J1-A1 is Line (L1), J1-A2 is Line 2/Neutral (L2/N), and J1-A3 is 
Earth Ground (G) for safety. 
 
A fault-clearing device, such as a fuse or circuit breaker, with a maximum 
15A rating at the power supply input is required for safety agency compli-
ance.  It should be sized to handle the start-up inrush current of 30A at 115 
VAC and 60A at 230 VAC. 

Rev. 05/11/2012    Mission Power Solutions        (760) 631-6846          [email protected]             Pg. 5

 

J1 Pin Out 

A1 

Line 1 

A2 

Line 2/Neutral 

A3 

Ground 

A1    A2    A3 

Содержание Javelin I

Страница 1: ...Supply Operator s Manual I II Power Supply Power Factor Corrected AC DC Switcher Operator s Manual and Quick Install Instructions www mpwrs com Rev 05 11 2012 Mission Power Solutions 760 631 6846 sal...

Страница 2: ...e Phase DC A1 L1 A1 A2 L2 N A2 A3 Earth Gnd A3 Earth Gnd Table 1 AC and DC Input Connections Status Control Connector J2 J2 1 and J2 9 are spare pins and are not used J2 2 and J2 4 are Signal Return p...

Страница 3: ...sitive load con nection and pin J3 6 to the negative load connection Attach load end of sense lines at the point where regulation is desired J3 2 and J3 8 provide DC OK and DC OK signals J3 3 and J3 7...

Страница 4: ...ith Auto Sense Output overcurrent overvoltage and overtemperature protection Ride through holdup time 20 ms at 1200W load Size 4 9 H x 7 0 W x 10 75 L 9 5 L for Javelin II Heavy duty ruggedized enclos...

Страница 5: ...power output to come up 15 30 ms later An auxiliary Vcc output of 5 VDC capable of sourcing up to 300mA is provided for peripheral use An output Inhibit Enable function is provided by using an optocou...

Страница 6: ...ame as Earth Ground on input power connector J1 Inhibit Enable J2 7 to J2 8 The Inhibit Enable control pins allow the output to be controlled with either inhibit or enable logic Con necting Inhibit J2...

Страница 7: ...voltage drop along the output power cables the output can be trimmed up or configured for Remote Sense Use stranded twisted pair 20 24 AWG wire for the Remote Sense lines Remote Sense can compensate f...

Страница 8: ...nals i e a fuse Use proper size wires to avoid overheating and excessive voltage drop Do not attempt to repair or modify the power supply in any manner Do not restrict airflow to the unit The cooling...

Страница 9: ...Javelin I II Power Supply Operator s Manual Mechanical Drawing Javelin I Rev 05 11 2012 Mission Power Solutions 760 631 6846 sales mpwrs com Pg 9...

Страница 10: ...Javelin I II Power Supply Operator s Manual Mechanical Drawing Javelin II page 1 Rev 05 11 2012 Mission Power Solutions 760 631 6846 sales mpwrs com Pg 10...

Страница 11: ...Javelin I II Power Supply Operator s Manual Mechanical Drawing Javelin II page 2 Rev 05 11 2012 Mission Power Solutions 760 631 6846 sales mpwrs com Pg 11...

Страница 12: ...W load Transient Surge IEC 801 5 level 3 Common Mode Normal Mode Dielectric Withstand Primary to Chassis GND 2121 VDC Primary to Secondary 4242 VDC Secondary to Chassis GND 500 VDC Output Parameter MI...

Страница 13: ...ower 55 C to 55 C M Grade Half Power 55 C to 70 C Product Weight 11 50 lbs 11 0 lbs Javelin II Dimensions 4 9 H 124 46mm x 7 0 W 177 8mm x 10 75 L 273 1mm 9 5 L 241 3mm for Javelin II Warranty 1 Year...

Страница 14: ...00 1200 1400 1600 1800 2000 0 20 40 60 80 100 Pout max Temperature Ambient C Maximum Output Power vs Temperature 400W 600W 800W 1200W 1600W 1800W Rev 05 11 2012 Mission Power Solutions 760 631 6846 sa...

Страница 15: ...Javelin I II Power Supply Operator s Manual Rev 05 11 2012 Mission Power Solutions 760 631 6846 sales mpwrs com Pg 15 Notes...

Отзывы: