62
Relay Input - QX-mini and FX-3500
9.3
Configuration Steps
9.3.1 FX-3500 Configuration
1.
Open FX-3500 configurator.
2.
Create a new job or open an existing job. Ensure to change “AP Start” to enable CLIP
devices on the loop as QX-mini reporting points will be configured as CLIP devices. “AP
Start” number may vary based on different applications.
3.
Click on the loop that has been wired to SLC terminal on the QX-mini Master.
4.
Configure the loop as shown in the window below.
Note:
In this particular example, relay output module (MIX-M500R) was used
to activate the EVAC zone. This module must be correlated to all the
alarm inputs in the job.
Figure 89 The addresses may vary depending on each application.
5.
Ensure all the addresses are correct and job is validated. Connect to the FX-3500 panel
and send the job.