SLC Integration - QX-mini and FX-3500 - Single Stage
59
8.4
Zone Correlations
Zone activation on QX-mini can be correlated to FACP.
8.5
SLC Address Configuration
•
Alarm Input
: In Figure 81 on page 55, Input Module address 201 is an example of any
alarm input in the job. It would need to be correlated to the Supervised Output module
address 209 to activate the EVAC zone on QX-mini.
•
Common Trouble
: This feature allows the QX-mini to report any trouble(s) back to the
FACP. Referring to Figure 81, address 203 is an example of trouble input. Configure the
type as “trouble input” in the FACP configurator.
•
Signal Silence
: This feature allows FACP to silence audible and visible devices on the
QX-mini.
• Audible and Visual signal silence: Configure this as a relay output module, address
204 (shown in Figure 81), and correlate it to “signal silence” common status in the
FACP configurator.
•
Paging/Message Active
: This feature reports to FACP when QX-mini has been
manually activated. For example, when microphone is active or a message has been
activated, trouble will report back to FACP. Configure this as an input module (Address
205 in Figure 81) in the FACP configurator, and select type as “building/property safety”.
•
AC Trouble
: This feature reports QX-mini AC failure to FACP. If QX-mini is configured
for “AC Loss Delay” then a trouble will only be reported after the delay. Configure this as
an input module (Address 206 in Figure 81), and select type as “trouble input” in the
FACP configurator.
•
Battery/Charger Trouble
: This feature reports to FACP when QX-mini has a battery or
battery charger trouble. Configure this as an input module (Address 207 in Figure 81),
and select type as “trouble input” in the FACP configurator as shown in Figure 81.
•
Earth Ground Fault
: This feature reports to FACP when there is a ground fault detected
on QX-mini system. Configure this as an input module (Address 208 in Figure 81) and
select type as “trouble input” in the FACP configurator.
15.
Ensure all the addresses are correct and job is validated. Connect to the FX-3500 panel
and send the job.