![background image](http://html1.mh-extra.com/html/mircom/openbas-hv-nx10-series/openbas-hv-nx10-series_installation-manual_1805795035.webp)
35 (45)
Field Wiring
120 VAC LED lamp
High impedance lamps such
as LED lamps require a 15 k
Ω
1W 5% resistor in parallel to
the lamp to prevent current
leakage.
120 VAC coil
Install a 120 V MOV surge
protector in parallel with
solenoid coil to suppress
noise.
24 VDC coil
Install a 1N4007 reverse
polarizing diode in parallel
with DC solenoid coil to
suppress flyback voltage.
24 VDC lamp
N/A
Table 8 Surge Protection on Relay Outputs (Continued)
Type of field
device
Notes
Wiring diagram
120 VAC LED
120 VAC
Neutral
NO
NC
C
Controller
Nȍ
120 VAC coil
120 VAC
Neutral
NO
NC
C
Controller
24 VDC coil
C
24 VDC
0 V
NO
NC
Controller
24 VDC lamp
24 VDC
0 V
C
NO
NC
Controller