![Mircom FX-LOC Скачать руководство пользователя страница 8](http://html1.mh-extra.com/html/mircom/fx-loc/fx-loc_installation-and-operation-manual_1805850008.webp)
Mircom
4
Wiring the Microphone and Selector Panel
Figure 4: QMP-5101N Network Master Paging Control Module Connections and Terminal Blocks
The interface wiring between the QMP-5101N, ANC-5000 and FX-LOC(R) is as follows:
The maximum wiring run from the QMP-5101N and the ANC-5000 is 20 feet or 6 metres.
MIC+, MIC-, SHLD:
18-22 AWG Twisted Shielded Pair
PTT+, PTT-:
18-22 AWG Twisted Pair
Note:
The Common Trouble LED on the QMP-5101N Paging Module is configured as MIC Active for
FX-LOC(R). Replace the Common Trouble label with the MIC Active label and re-configure the Common
Trouble LED using the FleX-Net
TM
configurator MSW-025.
TO P1 OF RAX-1048TZDS
CABLE CONNECTS TO
RAXN-LCD
FACTORY WIRED
TO MICROPHONE
FROM PREVIOUS
MICROPHONE
OR ANC-5000
TO NEXT
MICROPHONE
(IF LAST MICRO-
PHONE PLACE TWO
EOL 3K9 ohm
RESISTORS HERE
B and -
OF MIC AND PTT
TERMINALS.
This drawing is a
representation of the
terminals. Follow wiring
as labelled. Location of
terminals may vary.