Mircom FX-LOC Скачать руководство пользователя страница 15

FX-LOC Local Operating Console

11

Warranty & Warning Information

Warning Please Read Carefully 

Note to End Users: This equipment is subject to terms and conditions of sale as follows:

Note to Installers 

This warning contains vital information. As the only individual in contact with system users, it is your responsibility to 
bring each item in this warning to the attention of the users of this system. Failure to properly inform system end-
users of the circumstances in which the system might fail may result in over-reliance upon the system. As a result, 
it is imperative that you properly inform each customer for whom you install the system of the possible forms of 
failure. 

System Failures 

This system has been carefully designed to be as effective as possible. There are circumstances, such as fire or 
other types of emergencies where it may not provide protection. Alarm systems of any type may be compromised 
deliberately or may fail to operate as expected for a variety of reasons. Some reasons for system failure include: 

Inadequate Installation

A Fire Alarm system must be installed in accordance with all the applicable codes and standards in order to provide 
adequate protection. An inspection and approval of the initial installation, or, after any changes to the system, must 
be conducted by the Local Authority Having Jurisdiction. Such inspections ensure installation has been carried out 
properly.

Power Failure

Control units, smoke detectors and many other connected devices require an adequate power supply for proper 
operation. If the system or any device connected to the system operates from batteries, it is possible for the 
batteries to fail. Even if the batteries have not failed, they must be fully charged, in good condition and installed 
correctly. If a device operates only by AC power, any interruption, however brief, will render that device inoperative 
while it does not have power. Power interruptions of any length are often accompanied by voltage fluctuations which 
may damage electronic equipment such as a fire alarm system. After a power interruption has occurred, 
immediately conduct a complete system test to ensure that the system operates as intended.

Failure of Replaceable Batteries

 

Systems with wireless transmitters have been designed to provide several years of battery life under normal 
conditions. The expected battery life is a function of the device environment, usage and type. Ambient conditions 
such as high humidity, high or low temperatures, or large temperature fluctuations may reduce the expected battery 
life. While each transmitting device has a low battery monitor which identifies when the batteries need to be 
replaced, this monitor may fail to operate as expected. Regular testing and maintenance will keep the system in 
good operating condition.

•Compromise of Radio Frequency (Wireless) Devices

 

Signals may not reach the receiver under all circumstances which could include metal objects placed on or near the 
radio path or deliberate jamming or other inadvertent radio signal interference.

•System Users

 

A user may not be able to operate a panic or emergency switch possibly due to permanent or temporary physical 
disability, inability to reach the device in time, or unfamiliarity with the correct operation. It is important that all 
system users be trained in the correct operation of the alarm system and that they know how to respond when the 
system indicates an alarm.

•Automatic Alarm Initiating Devices

 

Smoke detectors, heat detectors and other alarm initiating devices that are a part of this system may not properly 
detect a fire condition or signal the control panel to alert occupants of a fire condition for a number of reasons, such 
as: the smoke detectors or heat detector may have been improperly installed or positioned; smoke or heat may not 

Содержание FX-LOC

Страница 1: ...LT 6039 Rev 1 Install ation and O peration Manual June 2015 FX LOC R Local Operating Console MGC Network Fire Alarm Control Panel Normal Condition June 17 2015...

Страница 2: ......

Страница 3: ...Wiring the Microphone and Selector Panel 4 QMP 5101N Network Paging Wiring for Mass Notification 5 RAX 1048TZDS Audio Indication for Mass Notification 6 RAX 1048TZDS Zone Display Module 6 Configuratio...

Страница 4: ......

Страница 5: ...us Control Unit and a Master Microphone to provide emergency audio Below the ACU is another RAXN LCD which annunciates the fire alarm system along with a Master Telephone for emergency use Below this...

Страница 6: ...e The FX LOC R is made up of a mechanical backbox a middle metal chassis which the modules are attached to and a front door with a Lexan window The backbox may be mounted either surface or flush mount...

Страница 7: ...iring is complete hook the door with the Lexan window and the inner door chassis onto the backbox Refer to figure below for assembly instructions Figure 3 FX LOC R Mechanical Assembly BACKBOX DOOR WIT...

Страница 8: ...Note The Common Trouble LED on the QMP 5101N Paging Module is configured as MIC Active for FX LOC R Replace the Common Trouble label with the MIC Active label and re configure the Common Trouble LED u...

Страница 9: ...Master Paging Module Remote Power Input G A Input IN RS 485 NOT USED Wire the Paging Bus to all other ANC 5000 Audio Network Controller Modules OUT to IN See document LT 894 for more details TWISTED S...

Страница 10: ...one RAX 1048TZDS Zone Display Module Figure 6 Zone Display Module RAX 1048TZDS Table 1 RAX 1048TZDS Zone Display Module Cable Function Connector Function P1 P1 Cable connects to P2 of previous display...

Страница 11: ...evels of messaging priority above and below fire alarm messaging For example one area of voice messaging may have 5 percent above normal zone priority which means that this area has the first level pr...

Страница 12: ...8 This screen capture shows selection of Node 2 as Mass Notification This screen capture shows input zone priority settings for the Mass Notification Node 2 Select Node 2 as the MNS Mass Notification...

Страница 13: ...re Central Control and the Mass Notification System They are mutually independent FX LOC R Emergency Response Operation 1 Access control of FX LOC R 2 Mass Notification Node will be notified of paging...

Страница 14: ...101N module at the MNS and within the associated FX LOC R s Standby 175 mA Max Alarm 175 mA Max Current Drain for Battery Calculations Example The following are the currents for the RAXN LCD to which...

Страница 15: ...wer any interruption however brief will render that device inoperative while it does not have power Power interruptions of any length are often accompanied by voltage fluctuations which may damage ele...

Страница 16: ...se sources such as stereos radios televisions air conditioners or other appliances or passing traffic Audible notification appliances however loud may not be heard by a hearing impaired person Telepho...

Страница 17: ...com defects caused by failure to provide a suitable installation environment for the products damage caused by use of the products for purposes other than those for which it was designed damage from i...

Страница 18: ...t to change or revision without prior notice at the sole discretion of the Company WARNING Mircom recommends that the entire system be completely tested on a regular basis However despite frequent tes...

Страница 19: ......

Страница 20: ...5 660 4113 Mircom 2015 Printed in Canada Subject to change without prior notice www mircom com U S A 4575 Witmer Industrial Estates Niagara Falls NY 14305 Tel 888 660 4655 905 660 4655 Fax 905 660 411...

Отзывы: