Mircom FX-LOC Скачать руководство пользователя страница 16

Mircom

12

be able to reach the alarm initiating device, such as when the fire is in a chimney, walls or roofs, or on the other side 
of closed doors; and, smoke and heat detectors may not detect smoke or heat from fires on another level of the 
residence or building. 

Software

Most Mircom products contain software. With respect to those products, Mircom does not warranty that the 
operation of the software will be uninterrupted or error-free or that the software will meet any other standard of 
performance, or that the functions or performance of the software will meet the user’s requirements. Mircom shall 
not be liable for any delays, breakdowns, interruptions, loss, destruction, alteration or other problems in the use of a 
product arising our of, or caused by, the software.

Every fire is different in the amount and rate at which smoke and heat are generated. Smoke detectors cannot 
sense all types of fires equally well. Smoke detectors may not provide timely warning of fires caused by 
carelessness or safety hazards such as smoking in bed, violent explosions, escaping gas, improper storage of 
flammable materials, overloaded electrical circuits, children playing with matches or arson. 

Even if the smoke detector or heat detector operates as intended, there may be circumstances when there is 
insufficient warning to allow all occupants to escape in time to avoid injury or death. 

•Alarm Notification Appliances

 

Alarm Notification Appliances such as sirens, bells, horns, or strobes may not warn people or waken someone 
sleeping if there is an intervening wall or door. If notification appliances are located on a different level of the 
residence or premise, then it is less likely that the occupants will be alerted or awakened. Audible notification 
appliances may be interfered with by other noise sources such as stereos, radios, televisions, air conditioners or 
other appliances, or passing traffic. Audible notification appliances, however loud, may not be heard by a hearing-
impaired person. 

Telephone Lines

 

If telephone lines are used to transmit alarms, they may be out of service or busy for certain periods of time. Also the 
telephone lines may be compromised by such things as criminal tampering, local construction, storms or 
earthquakes. 

•Insufficient Time

There may be circumstances when the system will operate as intended, yet the occupants will not be protected from 
the emergency due to their inability to respond to the warnings in a timely manner. If the system is monitored, the 
response may not occur in time enough to protect the occupants or their belongings. 

•Component Failure

 

Although every effort has been made to make this system as reliable as possible, the system may fail to function as 
intended due to the failure of a component. 

•Inadequate Testing

 

Most problems that would prevent an alarm system from operating as intended can be discovered by regular testing 
and maintenance. The complete system should be tested as required by national standards and the Local Authority 
Having Jurisdiction and immediately after a fire, storm, earthquake, accident, or any kind of construction activity 
inside or outside the premises. The testing should include all sensing devices, keypads, consoles, alarm indicating 
devices and any other operational devices that are part of the system. 

•Security and Insurance

 

Regardless of its capabilities, an alarm system is not a substitute for property or life insurance. An alarm system also 
is not a substitute for property owners, renters, or other occupants to act prudently to prevent or minimize the 
harmful effects of an emergency situation. 

IMPORTANT NOTE: End-users of the system must take care to ensure that the system, batteries, telephone lines, 
etc. are tested and examined on a regular basis to ensure the minimization of system failure. 

Содержание FX-LOC

Страница 1: ...LT 6039 Rev 1 Install ation and O peration Manual June 2015 FX LOC R Local Operating Console MGC Network Fire Alarm Control Panel Normal Condition June 17 2015...

Страница 2: ......

Страница 3: ...Wiring the Microphone and Selector Panel 4 QMP 5101N Network Paging Wiring for Mass Notification 5 RAX 1048TZDS Audio Indication for Mass Notification 6 RAX 1048TZDS Zone Display Module 6 Configuratio...

Страница 4: ......

Страница 5: ...us Control Unit and a Master Microphone to provide emergency audio Below the ACU is another RAXN LCD which annunciates the fire alarm system along with a Master Telephone for emergency use Below this...

Страница 6: ...e The FX LOC R is made up of a mechanical backbox a middle metal chassis which the modules are attached to and a front door with a Lexan window The backbox may be mounted either surface or flush mount...

Страница 7: ...iring is complete hook the door with the Lexan window and the inner door chassis onto the backbox Refer to figure below for assembly instructions Figure 3 FX LOC R Mechanical Assembly BACKBOX DOOR WIT...

Страница 8: ...Note The Common Trouble LED on the QMP 5101N Paging Module is configured as MIC Active for FX LOC R Replace the Common Trouble label with the MIC Active label and re configure the Common Trouble LED u...

Страница 9: ...Master Paging Module Remote Power Input G A Input IN RS 485 NOT USED Wire the Paging Bus to all other ANC 5000 Audio Network Controller Modules OUT to IN See document LT 894 for more details TWISTED S...

Страница 10: ...one RAX 1048TZDS Zone Display Module Figure 6 Zone Display Module RAX 1048TZDS Table 1 RAX 1048TZDS Zone Display Module Cable Function Connector Function P1 P1 Cable connects to P2 of previous display...

Страница 11: ...evels of messaging priority above and below fire alarm messaging For example one area of voice messaging may have 5 percent above normal zone priority which means that this area has the first level pr...

Страница 12: ...8 This screen capture shows selection of Node 2 as Mass Notification This screen capture shows input zone priority settings for the Mass Notification Node 2 Select Node 2 as the MNS Mass Notification...

Страница 13: ...re Central Control and the Mass Notification System They are mutually independent FX LOC R Emergency Response Operation 1 Access control of FX LOC R 2 Mass Notification Node will be notified of paging...

Страница 14: ...101N module at the MNS and within the associated FX LOC R s Standby 175 mA Max Alarm 175 mA Max Current Drain for Battery Calculations Example The following are the currents for the RAXN LCD to which...

Страница 15: ...wer any interruption however brief will render that device inoperative while it does not have power Power interruptions of any length are often accompanied by voltage fluctuations which may damage ele...

Страница 16: ...se sources such as stereos radios televisions air conditioners or other appliances or passing traffic Audible notification appliances however loud may not be heard by a hearing impaired person Telepho...

Страница 17: ...com defects caused by failure to provide a suitable installation environment for the products damage caused by use of the products for purposes other than those for which it was designed damage from i...

Страница 18: ...t to change or revision without prior notice at the sole discretion of the Company WARNING Mircom recommends that the entire system be completely tested on a regular basis However despite frequent tes...

Страница 19: ......

Страница 20: ...5 660 4113 Mircom 2015 Printed in Canada Subject to change without prior notice www mircom com U S A 4575 Witmer Industrial Estates Niagara Falls NY 14305 Tel 888 660 4655 905 660 4655 Fax 905 660 411...

Отзывы: