59
Appendix B: Using the Configurator
Select the amplifier type. Choose from a single 60 Watt amp., 2*30 Watt or 4*15.
Choose the bin and slot for the location of the amplifiers. The program will suggest the next
available, suitably aligned location, but you can choose another that does not immediately
follow those amplifiers that are already configured.
Check the silencable box if the new amplifiers can be silenced.
Click the add button to add the amplifiers. The dialog remains open so that you can add more.
The Slot and Bin locations are recalculated.
Add Audio
This dialog is displayed in response to an Add Audio command.
Master Hand Set: You must specify whether the Audio Controller will support a master
handset (there must be at least one per job). If you choose to support a master handset, it will
consume one of the five lines of the controller.
Conventional Phones or Voice Lines: You must specify whether the four (or five) lines are to
be configured as conventional phones or as voice lines to serve addressable phone modules.
After the Audio Controller is added you can still edit these attributes, or change just some of
the lines between voice and conventional.
Add Circuit Adder
This dialog is displayed in response to an Add Circuit Adder command, or an Add Device
when the selected tree item is a conventional (hard wired) loop.
Examples:
Add 8 Input Adder - 8 Ckts: Will add additional DM-1008A Input Module with 8 Class B (4
Class A) Input Circuits
Add Supv Opt.adder 4 Ckts: Will add a SGM-1004A Signal Module with 4 Supervised Output
Circuits
Add Relay Opt - 8 ckts: Will add RM-1008A Relay module with 8 Relay circuits.
After the operation is complete the dialog remains open for re-use. The Close button
dismisses the dialog.