116
Appendix B: Using the Configurator
•
Audio
•
Audio Setup... - launches the Audio Setup dialog.
•
Timers
•
Auto GA Timer - Choose from 0-30 minutesor Disabled. The control is disabled
unless Two Stage Operation is selected
•
Auto signal silence timer - Choose from 0-30 minutes or Disabled. The auto
signal silence timer cannot be set shorter that auto GA or signal silence inhibit
timers.
•
Signal silence inhibit timer - 0-3 minutes
•
Proving delay time - 5-90 seconds
•
Power-fail delay for trouble transmit. If the only trouble on the system is an AC
power failure, transmision of the status through the UDACT can be delayed up
to 18 hours
•
New Alarm - 10-120 seconds. The timer is started by a new alarm. When it
expires, the new alarm system status is cleared. It is stopped by system reset.
•
Auto Resound – 5-12 minutes. The timer is started by the New Alarm Active
Timer timeout event. When it expires, the system status
STAT_AUTO_SUITE_RESOUND is set. The timer is stopped by (1) new alarm
(2) Alarm Acknowledge or (3) system reset.
•
Page Inhibit – 10-120 seconds. Started by the first active alarm. Paging is
inhibited while the timer is running. The internal system status Page Inhibit is
TRUE while the timer is running.
•
Date and Time
•
Daily clock adjustment:
- Specifies the number of seconds (positive or negative) by which the panel's
clock is to be adjusted every 24 hours. The adjustment, if any, is made at 01:55
every day.
•
Daylight Saving:
- Enable Daylight Saving - Enables automatic change to and from daylight
saving. The rules specifying when daylight saving time begins and ends are
specified below.
•
After Hours:
- Enable Auto After Hours
- Daytime Start and End - specify when daytime begins and ends.
- Weekend Start and End - specify when the weekend begins and ends.
- Holidays - list the defined holidays.
- Modify... - open the Edit Holidays dialog
- Reprogram Holiday Trouble - check this box to put the panel into trouble when
there are no future holidays programmed. Specify the date after which there are
no programmed holidays. The panel will be in trouble until the job is re-
configured to have more holidays or the check box is un-checked.