143
43.1 QMP-5101N Network Paging Wiring for Mass Notification
QMP-5101N Network Master Paging Control Module Wiring to the ANC-4000 Audio Network Controller
Module
JW7
JW8
+ - + -
S - +
S - +
S - +
S - + L - +
PAGING BUS
MIC
PTT
OUT
IN
ANC-4000 Audio
Network Controller
Module in the
MNS (ACU)
+
+
-
-
S
PTT
MIC
QMP-5101N Network
Master Paging Module
+
+
-
-
S
PTT
MIC
QMP-5101N Network
Master Paging Module
Remote
Power
Input
G.A.
Input
IN
RS-485
NOT USED
Wire the Paging Bus
to all other ANC-4000
Audio Network
Controller Modules
OUT to IN.
TWISTED
SHIELDED
PAIR CABLE
TWISTED
SHIELDED
PAIR
CABLE
Jumpers JW7 and JW8
must be installed at all
times.
This connec-
tion to Aux
Power is not
required when
ANC-4000 is
installed in the
Audio Card
Cage
Daisy chain PTT and
MIC to next FX-LOC(R).
At the last FX-LOC(R)
QMP-5101N Paging
Mocule connect EOL
resistors (3K9 ohms
value) to + and - of
both the MIC and PTT
terminals.
MNS - ACU
FX- LOC(R)