40
5.11
Hardwire Signal Adder Module (SGM-1008A)
Figure 20
Hardwire Signal Adder Module (SGM-1004A)
5.11.1 Basic Mode
Jumpers on the SGM-1004A Signal Adder Module and their functions:
JW1:
Remove continuity jumper if this is not the last adder module installed.
JW2, JW3, JW4, and JW5:
Leave these jumpers open, on positions 2 and 3.
J11 Terminals:
Not connected.
5.11.2 Components
There are four green LEDs on the board, one for each signal zone. The LED will illuminate or
flash following the signal rate sent to its zone. It will be off when the system is normal and they
will illuminate when a signal zone is activated. The LED does not reflect what is happening on
the signal zone, just that it is receiving data to activate that signal zone.
5.11.3 Operation
There are two modes of operation for this module. The basic mode of operation does not
involve any isolators connected to the signal zones. For this case, leave jumpers JW2, JW3,
JW4 and JW5 as they come on pins 2 and 3, and do not make any connection to terminal
block J11. The isolator mode is used when isolators are to be connected to the signal circuits.
For further information on bell cut relays or isolators, please refer to the specific fire alarm
panel manual or the isolator instruction manual.
Note:
Jumpers JW2, JW3, JW4 and JW5 are positioned on pins 2 and 3 (right two pins with
board orientation as shown above) from factory.
P1
P3
P4
FIELD WIRING
TERMINALS
P2
JW1
JW5
JW4
JW3
JW2
J11
1 2 3
GREEN SIGNAL LEDs
ZONE 4
ZONE 3
ZONE 2
ZONE 1
Data cable to P6 or P5 of
main fire alarm module
or to P13 or P12 of loop
controller module, previ-
ous adder module
Power connector to P8 of
main fire alarm module, or
to P2 of loop controller
module, or to previous
adder module
Power connector for
next adder module
Data connector for
next adder module
1
2