SMALL-SIZE EXPLOSIVE GAS MEASURING
SENSOR MIPEX-02-X-X-X.1 X (RX)
ESAT.413347.005 UM
Revision 3.0
January 19th, 2017
Page 24 of 46
THE SOLE PROPERTY OF OPTOSENSE LLC. ANY REPRODUCTION WITHOUT THE WRITTEN PERMISSION OF OPTOSENSE LLC IS PROHIBITED.
Table 6. Basic sensor readings variability
7
Calibration
gas
Readings variability within a temperature
range
Additional variabil-
ity due to pressure
Additional variabil-
ity due to humidity
CH
4
±0.1% vol. or ±5% of indication (whichever is
greater) within the range of +20…+25 °C;
±0.2% vol. or ±30%
of indication (which-
ever is greater) at
100 kPa (test: 80
kPa, 100 kPa, 120
kPa)
±0.2% vol. or ±15%
of indication (which-
ever is greater) at
40 °C (test: 20%
RH, 50% RH, 90%
RH)
±0.2% vol. or ±10% of indication (whichever
is greater) within the range of -
10…+20 °C
and +25…+40 °C;
±0.4% vol. or ±20% of indication (whichever
is greater) within the range of -
40…-10 °C
and +40…+60 °C.
C
3
H
8
, CO
2
±0.05% vol. or ±5% of indication (whichever
is greater) within the range of +20…+25 °C;
±0.1% vol. or ±30%
of indication (which-
ever is greater) at
100 kPa (test: 80
kPa, 100 kPa, 120
kPa)
±0.1% vol. or ±15%
of indication (which-
ever is greater) at
40 °C (test: 20%
RH, 50% RH, 90%
RH)
±0.1% vol. or ±10% of indication (whichever
is greater) within the range of -
10…+20 °C
and +25…+40 °C;
±0.2% vol. or ±20% of indication (whichever
is greater) within the range of -
40…-10 °C
and +40…+60 °C.
Fig. 7. Typical sensitivity of MIPEX-02-1-X-X.1 X (target and calibration gas is CH
4
) to other
hydrocarbons
7
The table shows basic variability of MIPEX-02 sensor readings. For each sensor modification,
readings variability stated in Table 6 is provided within a temperature range determined by a sensor RX-code
(see Table 5).
0
50
100
150
200
250
0
20
40
60
80
100
120
S
enso
r
rea
d
ing
s,
%
L
E
L
CGM concentration, % LEL
CH4
C3H8
C2H6
C4H10
C6H14
C2H4