1. Remove the circuit breaker plate from the UPS and punch out the
knockout hole
2. Attach conduit to the conduit hole and route output wiring to the termi-
nal block.
3. Connect the output wiring according to Table 3-9, Output Circuit
Breaker Chart. Figure 3-21 shows the circuit breaker terminal block
labels.
Table 3-9. Output Circuit Breaker Wiring Chart
Load to Circuit Breaker Plate
Connect This Wire
To This Terminal on the Output Circuit Breaker
Output Ground
Grounding Stud
Output Neutral
N (Neutral)
Output Line 1 (hot)
L1 (Line 1)
Output Line 2 (hot)
L2 (Line 2)
L2 L1 N
USE CU ONLY
05143228 A
Figure 3-21. Output Circuit Breaker
4. Reattach the output circuit breaker plate to the UPS. Go to the section
4, Operation, under Using Options for instructions about operating the
load circuit breaker.
I
NTERFACE
P
ORTS
The interface ports are located at the back of the UPS. They include a relay
interface port, an RS-232 port, and a remote emergency power off (REPO)
switch port. This section describes the function and location of each port.
Figure 3-22 shows each ports location.
RELAY INTERFACE PORT
The relay interface port has dry contacts that provide connections for a number of
remote status display and remote alarm devices. These devices include:
AC line failure alarm
Impending low battery alarm
Summary alarm
Load-on-bypass alarm