Minuteman Continuous Power Series UPS
4.
Remove the rear panel plates at the back of the UPS as shown
in Figure 3-4.
The two sets of terminal blocks consist of seven
(7) terminals each. Six (6) of the terminals on the AC input and
battery input block are used for connections. The remaining
terminal is not connected. Follow the terminal block labels
when connecting wires.
Exposed
Terminal
Blocks
Removed
Rear Panel
Plates
Removed
Plug Cap
Knockout
from second
conduit hole
Figure 3-4. Removing the Rear Panel Plates and Plug Cap
5.
Remove plug cap and knockout and attach conduit.
Remove
the plastic plug cap from the conduit hole and attach flexible
wiring conduit to the conduit hole. Create a second conduit
hole by punching out a knockout from one of the rear panel
plates, as shown in Figure 3-4, and attach a second conduit.
6.
Route the input and output wiring.
Route the wiring for the AC
input and loads through separate conduit to the terminal
blocks.
C A
C A
C A
C A
C A U T I O N
U T I O N
U T I O N
U T I O N
U T I O N
Avoid damage. Do not remove, cut, or modify
any of the
wiring connected to the terminal blocks by the factory. For
input wiring, connect only ONE WIRE to each terminal. For
output wiring, more than one wire may be connected to a
terminal. The UPS or your load may be damaged if any of
the factory-installed wiring is cut, broken, removed, or modi-
fied in any way.
N O
N O
N O
N O
N O T E
T E
T E
T E
T E
The National Electrical Code requires that a current limiting
device (
provided by the customer
) must be installed be-
tween the input line to the UPS and between the UPS and
the output line when hard wired.
7.
Connect a current limiting device between the AC input and
the UPS.
Refer to Table 3-1 for the recommended circuit
breaker size for each model.
CAUTION!
NOTE