2 4
STEPS FOR INSTALLING THE TRANSFORMER AND UPS
1. Select the input and output wiring for the UPS and transformer. If the
UPS is already installed, go to step 3. The transformer and UPS use
#10 AWG size wire torqued to 35 in-lb. Use only copper conductors
and follow all pertinent local electrical codes.
2. Provide an AC input line that meets both the UPSs and transformers
electrical requirements. Verify that the operation of the transformer and
UPS does not exceed the rated capacity of the circuit (the rating of the
external circuit breakers must match the AC input rating).
3. Remove the rear panel plates from the transformer and the UPS to
expose the terminal blocks.
4. If the UPS is already installed, disconnect the AC input from the UPS
terminal blocks according to Table 3-4, UPS Disconnect Chart. If the
UPS is not installed, go to step 6.
W A R N I N G
W A R N I N G
W A R N I N G
W A R N I N G
W A R N I N G
ELECTRICAL SHOCK HAZARD. The hardwired transformers must
be installed by a
qualified electrician
or
technician
, or some
other qualified personnel. The UPS and batteries may contain
HIGH VOLTAGES. These high voltages can injure or kill personnel
and damage equipment.
Table 3-4. UPS Disconnect Chart
Disconnecting AC Input from the UPS
Disconnect This Wire
From This Terminal on the UPS
Utility GROUND
Grounding Stud
Utility Neutral
IL3 (Neutral)
Utility Line 1 (hot)
IL1 (Line 1)
Utility Line 2 (hot) two-phase only
IL2 (Line 2) two-phase only
5. Remove the AC input wiring from the UPS conduit.
6. Remove the two knockouts from the rear panel plates of the transformer
and attach flexible conduit to each hole.
7. Route the AC input and output wiring through each conduit to the
terminal blocks of the transformer.
C A
C A
C A
C A
C A U T I O N
U T I O N
U T I O N
U T I O N
U T I O N
Avoid damage. Do not remove, cut, or modify
any of the
wiring connected to the terminal blocks by the factory. For
input wiring, connect only ONE WIRE to each terminal. For
output wiring, more than one wire may be connected to a
terminal. The UPS or your load may be damaged if any of
the factory-installed wiring is cut, broken, removed, or modi-
fied in any way.
Section 3
Installation
WARNING!