3 0
External Battery
External Battery
UPS
External
Battery
Line Cord
External
Battery
Connector
Ext. Battery
Connector
Figure 3-18. Connecting Battery Packs to the UPS
RECONFIGURING RUN TIME AND LOW BATTERY WARNING
Adding external batteries requires you to reconfigure the UPSs battery run
time and low battery warning. To accomplish this, a program disk called
PWRS Battery Upgrade is included with your external battery pack(s).
System Requirements:
DOS 2.0 or greater; or
Windows 3.0 or greater.
After connecting the external battery pack(s), follow the steps below to use the
PWRS Battery Upgrade program.
1. Connect the UPS to a host computer through the RS-232 port using
the interface cable that accompanied your UPS.
2. Place the PWRS Battery Upgrade disk in the computers floppy drive.
3. If you are using DOS, type Battery n at the prompt (n= the number of
external battery packs connected to the UPS. For example, if you have
connected 2 battery packs, enter Battery 2). Then press return.
4. If you are using Windows, select FILE from the Program Manager and
choose Run. At the command line enter Battery n (n= the number of
external battery packs. For example, if you are connecting 2 battery
packs, enter Battery 2). Then click OK.
5. The program takes several seconds to run. After the program has run
the UPS will calculate the correct battery run time and give an accurate
low battery warning. Save the disk for future upgrades.