The DC Breaker connects and disconnects the DC bus voltage from the Battery
Pack to the UPS. The DC Breaker will trip in the event of a DC overcurrent condi-
tion.
2.
The External Battery connector is for Daisy Chaining additional Battery Packs.
3.
The External Battery cable is for connecting the Battery Pack to the UPS or Daisy
Chaining additional Battery Packs.
INSTALLATION PLACEMENT
This Battery Pack series is
ONLY
intended to be installed in an indoor tem-
perature controlled environment that is free of conductive contaminants. DO
NOT operate the Battery Pack in: extremely dusty and/or unclean areas, loca-
tions near heating devices, water or excessive humidity, or where the Battery
Pack is exposed to direct sunlight. Select a location, which will provide good
air circulation for the Battery Pack at all times.
Route the battery cables so
they cannot be walked on or damaged. This Battery Pack series is not for use
in a computer room as defined in the Standard for the Protection of Electronic
Computer/Data Processing Equipment ANSI/NFPA 75. Typical battery life is 3
to 5 years. Environmental factors do affect battery life. High temperatures,
poor utility power, and frequent, short duration discharges have a negative
impact on battery life.
INSTALLATION
Be sure to read the installation placement and all the cautions before installing
the Battery Pack. Place the Battery Pack in the final desired location and
complete the rest of the installation procedure.
WARNING!
These Battery Packs are extremely heavy. Anytime the Battery
Pack has to be handled be sure to use, enough personnel, strong supports
and equipment to safely handle the Battery Pack.
CAUTION! DO NOT
install these Battery Packs with its front or rear panel
facing down at any angle or laying on its side panels.
Chapter 2: Rear Panel
Chapter 3: Installation
NOTE:
When using these Battery Packs, the UPS must be configured so that
the UPS will report the correct estimated runtime on the LCD screen and in the
Power Monitoring software and/or the SNMP card. See the Power Monitoring
software or the SNMP card’s User's Manual to configure the UPS.
Operating Temperature (Maximum): 0 to 40°C (+32 to +104°F)
Operating Elevation: 0 to 3,000m (0 to +10,000 ft)
Operating and Storage Relative Humidity: 10% to 90%, non-condensing
Storage Temperature: -15 to +45°C (+5 to +113°F)
Storage Elevation: 0 to 15,000m (0 to +50,000 ft)