![Minebea Intec Maxxis 5 Скачать руководство пользователя страница 55](http://html1.mh-extra.com/html/minebea-intec/maxxis-5/maxxis-5_original-installation-manual_1801172055.webp)
Technical data
Description
Data
Connection
2 x terminal, 6-pin
Number of outputs
4 (CH1, CH2, CH3, CH4)
Output
Change-over contact
Max. switching voltage: U
DC
= 31 V/U
AC
= 24 V
Max. switching current: 1 A
Switching frequency
Max. 10 Hz
Potential isolation
Free relay change-over contact
Cables
Screened
Connect the cable screen (wire gauge max. 1.5 mm
2
) to the
device screen clamping rail.
Cable length
Max. 50 m
Coding pin
Is inserted in the position marked in gray in the image
4 Device installation
Process Controller Maxxis 5 PR 5900
Minebea Intec
EN-53