LED status
Description
Comments
Flashing green
Module is online
No connection
Constant red
Critical connection error
-
Duplicate IP address
-
Severe error
Flashing red
One or more connections has excee-
ded the connection time (CIP class 1
or 3).
Module status (MS)
LED status
Description
Comments
Of
Module is oline
No power
Constant green
Normal operation
Controlled by a scanner (run state).
Flashing green
Idle
-
No coniguration
-
Scanner is in the idle state.
Constant red
Exception error
-
Module has the status "EXCEPTI-
ON"
-
Severe error
-
etc.
Flashing red
Error that can be correc-
ted
The module is conigured but the sa-
ved parameters are diferent from tho-
se being used.
4.6.12.2
Connection
1. Guide the cable (e.g., patch cable CAT5) into the instrument through the metal sleeve
of the cable gland, strip the insulation, and mount the supplied RJ-45 plug (see
mounting information for connector).
2. Insert the RJ-45 plug into the RJ-45 socket of the ieldbus card.
3. Tighten the cable gland of the instrument.
Process Controller Maxxis 5 PR 5900
4 Device installation
EN-120
Minebea Intec