21
●
[
F-09
]
Accumulated Value Hold Selection
The default setting is "OFF", the accumulated flow value is
zeroed when the power supply is turned off.
Select this function to keep accumulated flow value to be
stored in permanent memory and reload the recent saved
accumulated value after power supply turns on.
Press or button at Function Setting Mode to display
[
F-09
] [
EEPr
].
Accumulated
Value Hold
Set Value
Press
button
Flashing
alternately
Display Refresh Time Setting
Press or button
to turn off the function
or select the data
stored cycle.
EEPr
off
Function "OFF"
Data stored
every 2 min.
Data stored
every 5 min.
EEPr
EEPr
EEPr
off
Flashing
alternately
Flashing
alternately
Flashing
alternately
F-09
EEPr
Flashing
alternately
Flashing
alternately
Press
button to return to
Function Selection Mode
DIGITAL FLOW SENSOR
( INSTRUCTION MANUAL )
MF01
How to use
–
Operation setting instructions
●
[
F-10
]
Flow Sensor Display Mode Selection
Select to display Instantaneous Flow or Accumulated Flow Mode.
Press or button at Function Setting Mode to display
[
F-10
] [
d1s
].
Display Flow
Selected Mode
Press
button
Flashing
alternately
Display Mode Selection
Press or button
to select display mode.
Instantaneous
Flow Mode
Accumulated
Flow Mode
Flashing
alternately
Flashing
alternately
F-10
Press
button to return to
Function Selection Mode
* NOTE: When the measured flow rate range is 500mL/min or 1000mL/min,
the accumulated flow is selected and the unit will become in mL/min.
NOTE
The maximum writable limit of the memory device is 1 million cycles.
If the sensor is operated 24 hours per day, the durability is calculated
as below:
● 5 minutes x 1 million cycles = 5 million minutes = 9.5 years
● 2 minutes x 1 million cycles = 2 million minutes = 3.8 years
dSp
dSp
dSp
1n5
1n5
ADD
d1S
5A1n
2A1n