OM-249 795 Page 26
5-9. Connecting To Weld Output Terminals
803 778-B
!
Stop engine.
!
Failure to properly connect
weld cables may cause ex-
cessive heat and start a fire,
or damage your machine.
Do not place anything between
weld cable terminal and copper
bar. Make sure that the sur-
faces of the weld cable terminal
and copper bar are clean.
1
Correct Weld Cable
Connection
2
Incorrect Weld Cable
Connection
3
Weld Output Terminal
4
Supplied Weld Output
Terminal Nut
5
Weld Cable Terminal
6
Copper Bar
Remove supplied nut from weld
output terminal. Slide weld cable
terminal onto weld output terminal
and secure with nut so that weld
cable terminal is tight against cop-
per bar.
Tools Needed:
4
2
3
1
3/4 in.
5
6
5-10. Selecting Weld Cable Sizes*
NOTICE
−
The Total Cable Length in Weld Circuit (see table below) is the combined length of both weld cables. For example, if the power source is
100 ft (30 m) from the workpiece, the total cable length in the weld circuit is 200 ft (2 cables x 100 ft). Use the 200 ft (60 m) column to determine cable
size.
!
Turn off power before
connecting to weld
output terminals.
Weld Output
Terminals
!
Do not use worn,
damaged, under-
sized, or poorly
spliced cables.
Weld Cable Size** and Total Cable (Copper) Length in Weld Circuit
Not Exceeding***
100 ft (30 m) or Less
150 ft
(45 m)
200 ft
(60 m)
250 ft
(70 m)
300 ft
(90 m)
350 ft
(105 m)
400 ft
(120 m)
Welding
Amperes
10
−
60%
Duty
Cycle
60
−
100%
Duty
Cycle
10
−
100% Duty Cycle
100
4 (20)
4 (20)
4 (20)
3 (30)
2 (35)
1 (50)
1/0 (60)
1/0 (60)
150
3 (30)
3 (30)
2 (35)
1 (50)
1/0 (60)
2/0 (70)
3/0 (95)
3/0 (95)
200
3 (30)
2 (35)
1 (50)
1/0 (60)
2/0 (70)
3/0 (95)
4/0 (120) 4/0 (120)
250
2 (35)
1 (50)
1/0 (60)
2/0 (70)
3/0 (95)
4/0 (120)
2x2/0
(2x70)
2x2/0
(2x70)
300
1 (50)
1/0 (60)
2/0 (70)
3/0 (95)
4/0 (120)
2x2/0
(2x70)
2x3/0
(2x95)
2x3/0
(2x95)
350
1/0 (60)
2/0 (70)
3/0 (95)
4/0 (120)
2x2/0
(2x70)
2x3/0
(2x95)
2x3/0
(2x95)
2x4/0
(2x120)
400
1/0 (60)
2/0 (70)
3/0 (95)
4/0 (120)
2x2/0
(2x70)
2x3/0
(2x95)
2x4/0
(2x120)
2x4/0
(2x120)
500
2/0 (70)
3/0 (95)
4/0 (120)
2x2/0
(2x70)
2x3/0
(2x95)
2x4/0
(2x120)
3x3/0
(3x95)
3x3/0
(3x95)
*
This chart is a general guideline and may not suit all applications. If cable overheats, use next size larger cable.
**Weld cable size (AWG) is based on either a 4 volts or less drop or a current density of at least 300 circular mils per ampere.
( ) = mm
2
for metric use
***For distances longer than those shown in this guide, call a factory applications rep. at 920-735-4505 (Miller) or 1-800-332-3281 (Hobart).
Ref. S-0007-J 2011
−
07