Complete Parts List is available at www.MillerWelds.com
OM-249 795 Page 22
!
Always ground generator frame to
vehicle frame to prevent electric
shock and static electricity hazards.
!
Also see AWS Safety & Health Fact
Sheet No. 29, Grounding of Portable
And Vehicle Mounted Welding Gen-
erators.
!
Bed liners, shipping skids, and
some running gear insulate the
welding generator from the vehicle
frame. Always connect a ground
wire from the generator equipment
grounding terminal to bare metal on
the vehicle frame as shown.
!
Use GFCI protection when operat-
ing auxiliary equipment. If unit does
not have GFCI receptacles, use
GFCI-protected extension cord. Do
not use GFCI receptacles to power
life support equipment.
1
Equipment Grounding Terminal (On
Front Panel)
2
Grounding Cable (Not Supplied)
3
Metal Vehicle Frame
Connect cable from equipment ground
terminal to metal vehicle frame. Use #8
AWG or larger insulated copper wire.
Electrically bond generator frame to ve-
hicle frame by metal-to-metal contact.
5-3. Grounding Generator To Truck Or Trailer Frame
rot_grnd2 2012
−
03
−
800 652-D
1
3
2
GND/PE
5-4. Installing Exhaust Pipe
253 857-A
!
Stop engine and let cool.
!
Engine backfire can cause se-
vere burns or other injuries.
Do not point exhaust pipe to-
ward control panel. Keep away
from exhaust outlet.
!
Do not point exhaust pipe to-
ward LP fuel tank (if equipped).
Do not point exhaust pipe to-
wards shielding gas tank (if
equipped).
!
Point exhaust pipe in desired
direction but always away
from front panel and direction
of travel.
Tools Needed:
1/2 in.