TM-4414 Page 13
Belt/Hydraulic-Drive Generator
210 193-B
I1
V4, Waveform A
V1, R1
V3
See Section 6-3 for
waveforms A,B
Test Equipment Needed:
Voltage Readings
a) Tolerance
−
±
10% unless
specified
b) Condition
−
70
°
F (21
°
C); cold
machine (no warm-up); no load
c) Weld/power rpm unless specified
d) Reference
−
single arrow:
reference to circuit common
(lead 42); double arrow:
reference to points indicated
e) Wiring Diagram
−
V1
Rotor: +25 volts DC at no load
±
20%; +75 volts DC at full load
±
10%
V2
Exciter: 150 volts AC
V3
Voltage Feedback: 240 volts AC
V4
Output (Odd Leg): 245 volts AC
V5
Output: 120 volts AC
V6
Generator Enable: +12 volts DC
when generator is enabled (On); 0
volts DC when not enabled (Off)
V7
Shutdown Signal: +12 volts DC
when shutdown is latched; 0 volts
DC when not latched
V8
PWM Signal: 0 to +15 volts DC
Amperage Readings
a) Tolerance
−
±
5% unless specified
b) Condition
−
70
°
F (21
°
C); cold
machine (no warm-up); no load
I1
1 amps DC (60 Hz)
No greater than 3.5 amps DC under load
I2
1 amps DC (60 Hz)
No greater than 3.5 amps DC under load
R3
R4
R5
V5
V2, R2
Содержание TM-4414K
Страница 4: ......
Страница 15: ...TM 4414 Page 11 Belt Hydraulic Drive Generator Notes...
Страница 27: ...TM 4414 Page 23 Belt Hydraulic Drive Generator 207 884 C...