A complete Parts List is available at www.MillerWelds.com
OM-279299 Page 17
Ref. Input13 2015
−
08
!
Installation must meet all National and
Local Codes
−
have only qualified per-
sons make this installation.
!
Disconnect and lockout/tagout input
power before connecting input con-
ductors from unit. Follow established
procedures regarding the installation
and removal of lockout/tagout
devices.
!
Always connect green or green/yellow
conductor to supply grounding termi-
nal first, and never to a line terminal.
See rating label on unit and check input volt-
age available at site.
1
Plug (NEMA Type 6-50P)
2
Receptacle
(NEMA Type 6-50R) Customer
Supplied
Wire receptacle according to the direct con-
nection method stated below and as shown,
and connect plug to receptacle or direct con-
nect input power as follows:
3
Input Power Cord
4
Disconnect Device (switch shown in the
OFF position)
5
Disconnect Device Grounding Terminal
6
Disconnect Device Line Terminals
7
Black And White Input Conductor (L1
And L2)
8
Green Or Green/Yellow Grounding
Conductor
Connect green or green/yellow grounding
conductor to disconnect device grounding
terminal first.
Connect input conductors L1 and L2 to dis-
connect device line terminals.
9
Over-Current Protection
Select type and size of over-current protec-
tion using Section 5-2 (fused disconnect
switch shown).
Connect plug to receptacle if hard wiring
method is not used.
Close and secure door on disconnect device.
Follow established lockout/tagout proced-
ures to put unit in service.
5-3. Connecting 1-Phase Input Power (Continued)
Notes
Work like a Pro!
Pros weld and cut
safely. Read the
safety rules at
the beginning
of this manual.