A complete Parts List is available at www.MillerWelds.com
OM-230 693 Page 18
4-12. Electrical Service Guide
Failure to follow these electrical service guide recommendations could create an electric shock or fire hazard. These recommenda-
tions are for a dedicated branch circuit sized for the rated output and duty cycle of the welding power source.
Input Voltage
200
230
460
575
Input Amperes At Rated Output
48
42
21
17
Max Recommended Standard Fuse Or Circuit Breaker Rating In Amperes
Circuit Breaker
1
, Time-Delay
2
60
50
25
20
Normal Operating
3
70
60
30
25
Min Input Conductor Size In AWG
4
8
8
12
14
Max Recommended Input Conductor Length In Feet (Meters)
96
(29)
127
(39)
206
(63)
209
(64)
Min Grounding Conductor Size In AWG
4
8
10
12
14
Reference: 2005 National Electrical Code (NEC) (including article 630)
1 Choose a circuit breaker with time-current curves comparable to a Time Delay Fuse.
2 “Time-Delay” fuses are UL class “RK5” .
3 “Normal Operating” (general purpose − no intentional delay) fuses are UL class “K5” (up to and including 60 amp), and UL class “H” ( 65 amp and
above).
4 Conductor data in this section specifies conductor size (excluding flexible cord or cable) between the panelboard and the equipment per NEC Table
310.16. If a flexible cord or cable is used, minimum conductor size may increase. See NEC Table 400.5(A) for flexible cord and cable requirements.
Содержание Millermatic 252
Страница 14: ...OM 230 693 Page 10...
Страница 25: ...A complete Parts List is available at www MillerWelds com OM 230 693 Page 21 Notes...
Страница 26: ...A complete Parts List is available at www MillerWelds com OM 230 693 Page 22 4 15 Weld Parameters...
Страница 27: ...A complete Parts List is available at www MillerWelds com OM 230 693 Page 23 226 650 B...
Страница 37: ...OM 230 693 Page 33 Notes...
Страница 38: ...OM 230 693 Page 34 SECTION 7 ELECTRICAL DIAGRAM Figure 7 1 Circuit Diagram...
Страница 39: ...OM 230 693 Page 35 229 485 A...