OM-4409 Page 22
SECTION 5
−
INSTALLATION
install3 8/06
−
Ref. 800 652 / Ref. 800 477-A / 803 274 / 804 712
!
Always securely fasten weld-
ing generator onto transport
vehicle or trailer and comply
with all DOT and other applica-
ble codes.
!
Always ground generator
frame to vehicle frame to pre-
vent electric shock and static
electricity hazards.
!
If unit does not have GFCI re-
ceptacles, use GFCI-protected
extension cord.
NOTICE
−
Do not install unit where
air flow is restricted or engine may
overheat.
See Section 4-4 for lifting eye rat-
ing.
See Section 5-2 for mounting in-
formation.
Grounding:
1
Equipment Grounding Terminal
(On Front Panel)
2
Grounding Cable (Not Supplied)
3
Metal Vehicle Frame
Connect cable from equipment
ground terminal to metal vehicle
frame. Use #10 AWG or larger insu-
lated copper wire.
Electrically bond generator frame to
vehicle frame by metal-to-metal contact.
GND/PE
1
2
3
18 in
(460 mm)
18 in
(460 mm)
18 in
(460 mm)
18 in
(460 mm)
18 in
(460 mm)
Movement
5-1. Installing Welding Generator
OR
OR
Grounding
!
Bed liners, shipping skids, and some running
gears insulate the welding generator from the
vehicle frame. Always connect a ground wire
from the generator equipment grounding termi-
nal to bare metal on the vehicle frame as shown.
OR
Location/Airflow Clearance
OR
Содержание Big Blue Air Pak
Страница 25: ...OM 4409 Page 21 4 13 Manufacturing Rating Label...
Страница 47: ...OM 4409 Page 43 SECTION 9 ENGINE GENERATOR MAINTENANCE 9 1 Engine Maintenance Label...
Страница 65: ...OM 4409 Page 61 SECTION 12 AIR COMPRESSOR DIAGRAM 209 059 A Figure 12 1 Circuit Diagram For Air Compressor...
Страница 66: ...OM 4409 Page 62 SECTION 13 CIRCUIT DIAGRAM Figure 13 1 Circuit Diagram For Welding Generator...
Страница 67: ...OM 4409 Page 63 221 915 C...