SECTION 8
−
OPERATING AUXILIARY EQUIPMENT
8-1. Generator Power Receptacles (Standard Models)
2
1
191 624
3
4
1
120 V 20 A AC GFCI
Receptacle GFCI1
2
240 V 30 A AC Twistlock
Receptacle RC1
Receptacles supply 60 Hz single-
phase power at weld/power speed.
If a ground fault is detected, GFCI
Reset button pops out and
receptacle does not work. Check
for faulty tools plugged in
receptacle. Press button to reset
GFCI1.
At least once a month, run en-
gine at weld/power speed and
press test button to verify GFCI
is working properly.
3
Circuit Breaker CB1
4
Circuit Breaker CB2
CB1 protects RC1 and the genera-
tor winding from overload. If CB1
opens, RC1 and GFCI1 do not
work. Place switch in On position to
reset breaker.
CB2 protects GFCI1 from overload.
If CB2 opens, GFCI1 does not
work. Press button to reset breaker.
If a circuit breaker continues to
open, contact Factory Autho-
rized Service Agent.
Generator power is not af-
fected by weld output.
Maximum output is 2.4 kVA/kW
from GFCI1 and 4 kVA/kW from
RC1. Maximum output from all re-
ceptacles is 4 kVA/kW.
EXAMPLE: If 13 A is drawn from
RC1, only 7 A is available at GFCI1:
(240 V x 13 A) + (120 V x 7 A) =
4.0 kVA/kW
Содержание Big Blue 402D
Страница 39: ...OM 495 Page 33 Return To Table Of Contents Notes...
Страница 43: ...OM 495 Page 37 Return To Table Of Contents Notes...
Страница 54: ...OM 495 Page 48 Return To Table Of Contents 9 2 Maintenance Label...
Страница 62: ...OM 495 Page 56 Return To Table Of Contents 10 2 Maintenance Label...
Страница 75: ...OM 495 Page 69 Return To Table Of Contents 215 302 A...
Страница 77: ...OM 495 Page 71 Return To Table Of Contents 216 530 A...
Страница 79: ...OM 495 Page 73 Return To Table Of Contents 215 303 A...
Страница 81: ...OM 495 Page 75 Return To Table Of Contents 216 531 A...
Страница 83: ...OM 495 Page 77 Return To Table Of Contents 215 298 A...
Страница 85: ...OM 495 Page 79 Return To Table Of Contents 215 299 A...
Страница 114: ......