background image

www.GateOpenerSafety.com

4-

Safety Test

4-1.

Activate each 

monitored device

and confirm the corresponding inputs’ red LEDs on MIM-62 

turn on.

4-2.

Activate the operator and confirm that each monitored device stops and/or reverses as expected. 

3-1.       If 

monitored devices

are not functioning, check for proper power connections, including polarity, if

necessary.

3-2.       If, after the Learn button is pressed, one or both outputs are in fault (yellow LED on), check to see

which red LEDs are on. Confirm the device is connected to the assigned channel. If it is working,
confirm the output of the safety device is connected properly to the input connector.

3-3.       If re-learning MIM-62 is necessary: 

(a) Press the Learn button to clear settings
(b) Press the Learn button to learn new settings

3-4.       If all 

monitored devices

and MIM-62 are working (no red or yellow LEDs), and the operator is still

reporting a fault, confirm MIM-62 outputs are connected properly to the operator’s inputs. Also,
confirm the Output Interface is set correctly (pulsed or relay), as stated in the operator’s manual.

3-

Troubleshooting

2-9.       When all monitored safety device inputs are connected, turn on the power to the operator. MIM-

62 should display a brief light test followed by blinking of the Output A and Output B indicators.
The Learn Mode LED on the rear panel will also be lit. This indicates that MIM-62 is in Learn
Mode, and will display the present condition of each input channel’s sensor:

(a) On: solid

Open circuit (faulty wiring or nothing connected)

(b) Blinking

10K ohm terminated sensor (no fault indicated)

(c) Off: solid

Normally Closed sensor (no fault indicated)

(d) Fast Blink

Pulsed sensor (no fault indicated)

If there is a fault, correct any wiring or make selection changes before proceeding.

Note: The LEDs behave differently in Learn Mode versus Run Mode.

2-10.     When all intended devices are connected and indicating no faults, momentarily press the Learn

button on the rear panel. The lights should flash, and then all the LEDs should go off, except the
green power LED. Test each entrapment device to confirm the associated red LED turns on when
the device is activated.

2-11.     At this point, MIM-62 should be operational and may be mounted to its mounting location.

Содержание MIM-62

Страница 1: ...nment Switch on the rear panel Use of all 6 inputs is not required Each of the Output circuits of MIM 62 may be set to Relay 10K termination or normally closed or Pulsed like photo eye output signals by the Output Type selection switch on the rear panel and Terminal Connection choice on P1 MIM 62 may be powered from any 12 or 24 VAC DC source that can supply at least 130 mA MIM 62 can provide an u...

Страница 2: ...ure 1 www GateOpenerSafety com INPUTS 1 2 top to bottom Input Com Power Power INPUTS 3 6 top to bottom Power Power Com Input COM P N C 10K COM P N C 10K 12 24 VAC DC 12 24 VAC DC Outputs A B connect to the appropriate safety device s input pulsed N C 10K on your operator s main board Connect to your operator s accessory power supply 12 24 VAC DC Inputs 1 2 must be used They are assigned to Output ...

Страница 3: ...y 10K or normally closed or P for Pulsed as required by your gate operator See Figure 3 2 8 Each device input can have a different output assignment Use the Input Output Assignment DIP switches to select A or B for each input that has a monitored device See Figure 3 Note Input Channels 1 and 2 are hard wired for Output A switch positions 1 and 2 are ignored Figure 2 Figure 3 All 4 Wire Devices I I...

Страница 4: ...tly pulsed or relay as stated in the operator s manual 3 Troubleshooting 2 9 When all monitored safety device inputs are connected turn on the power to the operator MIM 62 should display a brief light test followed by blinking of the Output A and Output B indicators The Learn Mode LED on the rear panel will also be lit This indicates that MIM 62 is in Learn Mode and will display the present condit...

Страница 5: ...ant to Part15 of the FCC Rules These limits are designed to provide reasonable protection against harmful interference in a residential installation This equipment generates uses and can radiate radio frequency energy and if not installed and used in accordance with the instructions may cause harmful interference to radio communications However there is no guarantee that interference will not occu...

Отзывы: