www.GateOpenerSafety.com

2-5.       Wire each of your 

monitored devices 

to the removable 4-pin connector as shown in Figure 2. If the

device is polarity sensitive, identify the correct common/ground wires. You do not need to use all 6
inputs.

2-6.       Plug the 

monitored device’s 

connector into an appropriate input, as indicated in Figure 1. 

2-7.       To assign signal Output Types, select either “R” for Relay (10K or normally closed), or “P” for

Pulsed, as required by your gate operator. See Figure 3.

2-8.       Each device input can have a different output assignment. Use the Input/Output Assignment DIP

switches to select A or B for each input that has a monitored device. See Figure 3. 

Note: Input Channels 1 and 2 are hard-wired for Output A; switch positions 1 and 2 are ignored.

Figure 2

Figure 3

All 4-Wire

Devices

I

INPUT(+)

INPUT(-)

PWR(-)

PWR(+)

OUTPUT

POWER

10K

Sensing Edge

INPUT(+)

INPUT(-)

PWR(-)

PWR(+)

10K

EDGE

2-Wire Pulsed

Photo-Eye

INPUT(+)

INPUT(-)

PWR(-)

PWR(+)

PHOTO

EYE

All 3-Wire

Devices

A

INPUT(+)

INPUT(-)

PWR(-)

PWR(+)

OUTPUT

POWER

Содержание MIM-62

Страница 1: ...nment Switch on the rear panel Use of all 6 inputs is not required Each of the Output circuits of MIM 62 may be set to Relay 10K termination or normally closed or Pulsed like photo eye output signals by the Output Type selection switch on the rear panel and Terminal Connection choice on P1 MIM 62 may be powered from any 12 or 24 VAC DC source that can supply at least 130 mA MIM 62 can provide an u...

Страница 2: ...ure 1 www GateOpenerSafety com INPUTS 1 2 top to bottom Input Com Power Power INPUTS 3 6 top to bottom Power Power Com Input COM P N C 10K COM P N C 10K 12 24 VAC DC 12 24 VAC DC Outputs A B connect to the appropriate safety device s input pulsed N C 10K on your operator s main board Connect to your operator s accessory power supply 12 24 VAC DC Inputs 1 2 must be used They are assigned to Output ...

Страница 3: ...y 10K or normally closed or P for Pulsed as required by your gate operator See Figure 3 2 8 Each device input can have a different output assignment Use the Input Output Assignment DIP switches to select A or B for each input that has a monitored device See Figure 3 Note Input Channels 1 and 2 are hard wired for Output A switch positions 1 and 2 are ignored Figure 2 Figure 3 All 4 Wire Devices I I...

Страница 4: ...tly pulsed or relay as stated in the operator s manual 3 Troubleshooting 2 9 When all monitored safety device inputs are connected turn on the power to the operator MIM 62 should display a brief light test followed by blinking of the Output A and Output B indicators The Learn Mode LED on the rear panel will also be lit This indicates that MIM 62 is in Learn Mode and will display the present condit...

Страница 5: ...ant to Part15 of the FCC Rules These limits are designed to provide reasonable protection against harmful interference in a residential installation This equipment generates uses and can radiate radio frequency energy and if not installed and used in accordance with the instructions may cause harmful interference to radio communications However there is no guarantee that interference will not occu...

Отзывы: