18
5. Maintenance
The working life of the detector is 5 years from power on, replace the device if you observe
Invalid indicator blinks.
The newly decorated or re-decorated room should be ventilated for some time before
installing the detector.
It’s suggested to press the Test button to check the LED indicators, buzzer and outputs
every month; besides, check if the device is online and send periodic status on the IoT
platform.
To ensure the air inlets are not blocked, wipe the device with a clean dry cloth, do not use a
very wet cloth, alcohol, harsh chemicals or detergents which may damage the detector.
Do not use a lighter or other gas to test the detector, which may damage the detector.
There is possible accuracy drift if you store without power for a long time in different
devices. If you prefer a more consistent reading with better precision, you can keep the
device powered on in clear air for some time according to the below list.
Storage Time (Power Off)
Operating Time
Less than 1 month
At least 2 days
1~6 months
At least 3 days
More than 6 months
At least 7 days
6. Device Payload
All data are based on following format (HEX), the Data field should follow little-endian:
Channel1
Type1
Data1
Channel2
Type2
Data2
Channel 3
...
1 Byte
1 Byte
N Bytes
1 Byte
1 Byte
M Bytes
1 Byte
...
For decoder examples please find files on
https://github.com/Milesight-IoT/SensorDecoders
.
6.1 Basic Information
GS101 reports basic information of the device whenever joining the network.
Channel
Type
Description
ff
01(Protocol Version)
01=>V1
09 (Hardware Version)
01 40 => V1.4
0a (Software Version)
01 14 => V1.14
0b (Power On)
Device is on
16 (Device SN)
16 digits