8
Mute: Press the button (≤3s)
when device is in alarm status
Steady Alarm Light On, While
Other Lights Off
Stop Beeping for 1
Minute
Reboot: Hold on the button for
3s to 10s
All Lights Blink Slowly
/
Reset to Factory Default: Hold
on the button for more than 10s
All Lights Blink Quickly
/
2.5 Dimensions(mm)
3. Operation Guide
3.1 Basic Configuration
1. Connect the outputs to the solenoid valve, fan or other devices.
2. Power on the detector via default power adapter and wait for about 180s for the warm-up
process. When the warm-up finishes, the buzzer will beep twice and all indicators will stop
blinking except for the Power indicator.
3. Press the Test button to check if the LED indicators and buzzer work properly, if the relay
output can open the fan and valve output can close the gas valve. After testing, everything will
recover back to normal status except the gas valve, please turn on the valve manually.
4. Download and install “Milesight ToolBox” App from Google Play or Apple App Store.
5. Enable NFC on the smartphone and launch Milesight ToolBox.
6. Attach the smartphone with the NFC area to the device to read device information. Basic
information and settings of the device will be shown on ToolBox App if it’s recognized
successfully. You can read and configure the device by tapping the Read/Write device on the
App. To order to protect the security of the device, please change the password when first
configuration. The default password is
123456
.