background image

KEYPAD FUNCTIONS

STATUS DISPLAY

10

 TECHNICAL DOCUMENTATION

The top line of the display on the Mikrofill 3 will provide information on the current status of the unit as well as 

the system that it is managing, providing information on any potential issues and / or faults as and when they 

occur.

The following status messages will be displayed on the unit based on current conditions:

If the unit displays any messages other than those detailed above, then there is likely a fault either with the unit 

or the system. For a list of possible fault displays, along with causes and remedies, please refer to 

pages 13

 and 

14

 of this technical documentation.

-

-

-

-

-

-

-

-

-

SYSTEM DATA

This button is used primarily to scroll through the various settings of the unit. Repeatedly pressing this 

button will cycle through each setting (see 

page 12

 for information on each of these settings). 

Pressing this button whilst the unit is in 

SERVICE MODE

 will again cycle through each setting, but in 

this mode the settings can now be adjusted (described in further detail on 

page 11

).

UP

When the unit is in 

SERVICE MODE

 this button is used to increase parameter values.

POWER

Pressing and holding this button for approximately 2 seconds will turn the unit on or off. When the 

unit is powered on, the display should always be illuminated.

NOTE: This button will turn the unit off, but it does not isolate power to the unit.

DOWN

When the unit is in 

SERVICE MODE

 this button is used to decrease parameter values. This button can 

also be used to view the calibration code for the unit’s pressure sensors by pressing and holding it 

down for 2 seconds. The top line of numbers displayed will relate to the calibration of the unit.

SERVICE MODE

This is a multi-function button that, when the unit is in operational mode, is used to mute the audible 

alarm conditions. Pressing and holding this button for approximately 8 seconds will put the unit into 

SERVICE MODE

 where various parameters can then be adjusted (described in further detail on 

page 11

).

PRESSURE CORRECT

The Mikrofill 3 continuously monitors the system pressure. When the system pressure is within set 

parameters, the unit will show this message on the display.

SYSTEM FILLING

This message indicates that the unit is currently filling the system to its target fill pressure.

FILLING STOPPED DUE TO LOW MAINS WATER PRESSURE

The Mikrofill 3 continuously monitors the inlet pressure. If this inlet pressure falls below an acceptable 

level (

within 0.3 bar of the current system pressure

) whilst the unit is attempting to fill the system then 

the unit will operate a safety shut-down, displaying this message. Once the incoming pressure is 

reinstated, the unit will return to operating as normal.

FREQUENT USE

There is a 

FREQUENT USE

 setting on the Mikrofill 3 which can be adjusted by accessing the 

SERVICE 

MODE

 (described in further detail on 

page 11

). If the unit cuts in to top up the system more than the 

number of times this setting is set to within a 24-hour period then the unit will alarm and display this 

message. This alert is for informational purposes as it informs that the unit is having to top up the 

system unusually often, suggesting there may potentially be a leak somewhere on the system.

Содержание 3

Страница 1: ...P R E S S U R I S A T I O N U N I T MIKROFILL 3 PRESSURISATION UNIT TECHNICAL DOCUMENTATION ISSUE 12 15 Rev 01 I N S P I R E D E F F I C I E N C Y ...

Страница 2: ......

Страница 3: ...cal Diagram Electrical Data Keypad Functions System Data Up Power Down Service Mode Status Display Pressure Correct System Filling Filling Stopped due to Low Mains Water Pressure Frequent Use Service Mode Adjusting Settings Parameter Functions Fault Diagnosis Status Fault Conditions Status Fault Conditions continued Manual Override Component List Maintenance Removing the Controls Assembly Cleaning...

Страница 4: ...t Start Current Fuse Rating Maximum Load BMS Relays CONNECTION DETAILS Cold Water Inlet System Outlet Drain via Tundish Maximum Inlet Pressure Maximum Cold Fill Pressure Nominal Flow Rate Dry Weight 1806078 230 Volt 1 Amp 1 Amp 3 Amp 5 Amp 15mm Compression 15mm Compression BSP 5 Bar 4 7 Bar 14 l min at 2 Bar 5 kg ...

Страница 5: ...ly or a boosted cold water supply The unit is supplied complete with all necessary isolating valves and incorporates a basket filter in the inlet ballofix valve A flexible hose is supplied with the unit which MUST be connected to the inlet ballofix valve as shown in the diagram to the left Failure to do so may result in damage to the inlet pressure sensor due to water hammer resulting in a SENSOR ...

Страница 6: ... in excess of 1000L capacity please contact our technical department IMPORTANT NOTE DRAIN Following every fill procedure the unit will discharge a small amount of water establishing an air break For this the unit is supplied fitted with a BSP tundish which must be connected to a suitable drain Mikrofill Systems Ltd cannot accept responsibility for any consequential damage caused by failure to conn...

Страница 7: ...M OF A TYPICAL INSTALLATION Please note that for the purpose of clarity system valves are not shown For systems exceeding 90 C contact our technical department on 03452 60 60 20 for advice Further installation guidelines can be found on page 05 of this technical documentation ...

Страница 8: ...ONS FOR FIXING IN MILLIMETRES A maximum size of No 8 screws or M4 bolts are to be used A minimum of 25mm clearance either side of the unit is required A minimum of 250mm clearance above the unit is required The unit must be fitted on a sound solid surface 262 205 170 177 ...

Страница 9: ...the unit will first need to be removed by unscrewing the PZ2 screw located on the underside Removing this cover will reveal a 12 way terminal block with each connection labelled 1 9 for the volt free relays see electrical installation diagram below Live Earth and Neutral The wiring can be passed through the cable glands on the underside of the unit through an opening in the front casing then conne...

Страница 10: ...w the calibration code for the unit s pressure sensors by pressing and holding it down for 2 seconds The top line of numbers displayed will relate to the calibration of the unit SERVICE MODE This is a multi function button that when the unit is in operational mode is used to mute the audible alarm conditions Pressing and holding this button for approximately 8 seconds will put the unit into SERVIC...

Страница 11: ...proximately 8 seconds The display will indicate that you are now in SERVICE MODE You can then release the button The button can now be used to scroll through the various settings To increase or decrease the value of a setting use the or buttons respectively After adjusting the settings the unit will save any changes made and return to its normal operating mode when no button is pressed for approxi...

Страница 12: ...which is calculated in minutes the less responsive the flood protection set at 0 00 to disable Lvl 1 Leak Alert protection refers to the amount of time in seconds that the unit will continue to fill the system once the cold fill pressure has been reached to prevent overshoot or undershoot of the fill pressure increasing the time prevents undershoot and decreasing it prevents overshoot warns of fre...

Страница 13: ... requires a dynamic mains pressure of 0 3 bar or more above its cold fill setting If the mains pressure usually satisfies this requirement then the cause of the mains pressure drop should be investigated The filter in the included mains inlet ballofix valve should be removed and cleaned to ensure flow into the unit is not being restricted see page 17 for details If the unit operates more than the ...

Страница 14: ...splay are fluctuating or the voltage is unstable when measured with a multimeter then there is likely an issue with the supply The unit can be powered from an alternative source or a power suppressor can be fitted to try and stabilise the incoming voltage to the unit In either case of SENSOR FAILURE the Mikrofill 3 can be put into MANUAL OVERRIDE to stop it from locking out any equipment on site d...

Страница 15: ...PRESSION CHECK VALVE Ø 15mm CHECK VALVE WITH FLOW REGULATOR Ø 15mm CONTROLS ASSEMBLY WITH SENSORS ISOLATION VALVE OUTLET 15mm COMPRESSION NORMALLY CLOSED SOLENOID VALVE NORMALLY OPEN SOLENOID VALVE O RING NITRILE 3mm I D x 3mm C S 11 12 13 14 15 16 17 18 19 MK3000034 MK3000017 MK3000028 MK3000029 MK3000019 MK3000020 MK3000021 MK3000024 MK3000025 O RING NITRILE 14 5mm I D x 3mm C S PCB POWER PIPE C...

Страница 16: ...PZ2 screwdriver to give access to the terminal block where the unit can then be disconnected electrically Once fully isolated and disconnected both mechanically and electrically the unit can be removed from the wall by unscrewing the slot head bolt on the topside of the unit and lifting then pulling the unit from its backplate With the unit removed from the wall the steps detailed on the following...

Страница 17: ...d be taken as the front and back casing will still be connected together with wiring If required the wiring can be separated using the plug and socket connectors so that the front casing can be fully detached Three PZ2 screws will be holding the manifold assembly in place inside the casing Unscrewing these will allow the entire assembly to be slid forward out of the casing granting easy access to ...

Страница 18: ...s Moat Redditch B98 9HL declare that the Mikrofill 3 pressurisation unit satisfies the essential requirements of the Electromagnetic Compatibility EMC Directive 2004 108 EC and the Low Voltage Directive LVD 2006 95 EC and is manufactured in accordance with the harmonised European standard BS EN 60730 1 2011 Signed by Steven Cherrington Technical Director United Kingdom 28th August 2015 ...

Страница 19: ...ISO 9001 Registered Quality Management 015 ...

Страница 20: ...North Moons Moat Redditch Worcestershire B98 9HL UK T 44 0 3452 60 60 20 F 44 0 3452 60 60 21 E info mikrofill com www mikrofill com Mikrofill Systems Ltd 11 Merse Road ...

Отзывы: