INSTALLATION
REV.0.03_COD.610078_A4
Page 16
3.2
Electrical connection
ATTENTION
Connection of the machine to the electrical
to the electrical supply
must be
made by qualified, skilled personnel.
Make sure that the power supply voltage reading corresponds to the voltage indicated
on the data tag
Check that the power supply voltage does not differ by more than 10% from its
nominal value.
The frequency of the power supply voltage must not differ by more than 1% of its
value.
Connection of the machine to the power supply must be provided with a ground
connection and an equipotential circuit as set forth by current standards.
Make sure that the electrical systems are efficiently grounded.
The ground conductor is to be connected to the ground terminal identified
by the standard symbol.
The machine is equipped with a terminal identified by the relative symbol for
equipotential connections between appliances (see rules for electrical
plants).
Connect the machine and the relative dedicated disconnection device (not supplied)
by using a power cable compatible with the electrical characteristics of the machine.
In case of prolonged take up of the machine it is recommended that you execute the
disconnection procedure of the electrical connection by placing the dedicated
disconnection device in "OFF" state.
The upstream electrical power line must be dimensioned and protected in accordance
with current local regulations.
ATTENTION
Please refer to the installation plan provided.