37 of 39
10-527-1 MN3024DIY REV A
MN3024DIY
User Manual
Maximum E
fficienc
y
>92 %
Overload
protection
Peak power
3000VA
(102% < load <1 10%) ± 10%: report error and turn off the output after 5 minutes;
(110% < load < 1 25%) ± 10%: report error and turn off the output after 10 seconds;
Load >125 % ± 10%: report error and turn off the output after 5 seconds;
Loaded motor
capability
1HP
Rated battery
input voltage
24V (Minimum starting voltage
22V)
Battery
voltage range
Undervoltage alarm/shutdown voltage/overvoltage alarm /overvoltage recovery... settable on LCD
screen)
Power saving
mode
Load ≤ 50W
AC charging
Battery type
Lead acid or lithium battery
Maximum
charge current
(Settable)
0-40A
Charge
current error
± 5Adc
Charge
voltage range
20 –33Vdc
Short circuit
protection
Circuit breaker and blown fuse
Circuit
breaker
specifications
30A
Overcharge
protection
Alarm and turn off charging after 1 minute
PV charging
Maximum PV
open circuit
voltage
100Vdc
PV operating
voltage range
30-100Vdc
MPPT voltage
range
30-95Vdc