
26 of 39
10-527-1 MN3024DIY REV A
MN3024DIY
User Manual
Parameter
no.
Parameter
name
Settings
Description
15
Battery
discharge
limit voltage
[15] 20V default
Battery discharge limit voltage; when the
battery voltage is lower than the point, the
output is turned off immediately ; the setting
range is 20V~ 26V, with a step of 0.2V. It is valid
for user -defined battery and lithium battery.
16
Battery
equalization
enable
[16] DIS
Equalizing charge is disabled
[16] ENA default
Equalizing charge is enabled, only valid for
vented lead-acid battery and sealed lead-acid
battery
17
Battery
equalization
voltage
[17] 29.2V
default
Equalizing charge voltage; setting range :
24V~ 29.2V, with a step of 0.2V; valid for vented
lead-acid battery and sealed lead-acid battery
18
Battery
equalized
time
[18] 120 default
Equalizing charge time ; setting range :
5min~900min, with a step of 5 minutes; valid
for vented lead-acid battery and sealed lead -
acid battery
19
Battery
equalized
time out
[19] 120 default
Equalizing charge delay ; setting range :
5min~900min, with a step of 5 minutes ; valid
for vented lead-acid battery and sealed lead-
acid battery
20
Battery
equalization
interval
[20] 30 default
Equalizing charge derating time, 0~30days,
with a step of 1 day ; valid for vented lead -acid
battery and sealed lead-acid battery
21
Battery
equalization
immediately
[21] DIS
Stop equalizing charge immediately.
[21] ENA default Start equalizing charge immediately.
22
Power saving
mode
[22] DIS default
Power saving mode disabled .
[22] ENA
When t
he power saving mode is enabled, if the
re
is no l
oad or less than 50W, the inverter
output is turned off after a delay for a certain
period of time. When the load is more than
50W, the inverter automatically restarts.
23
Restart when
over load
[23] DIS
Automatic restart when overload is disabled. If
an overload occurs and the output is turned off,
the unit will not restart .