
27 of 39
10-527-1 MN3024DIY REV A
MN3024DIY
User Manual
Parameter
no.
Parameter
name
Settings
Description
[23] ENA default
Automatic restart when overload is enabled
.
If
an overload occurs and the output is turned off,
the unit will restart after a delay of 3
minutes . After it reaches 5 cumulative times,
the
unit
will not restart.
24
Restart when
over
temperature
[24] DIS
Automatic restart when over temperature is
disabled. If an over -temperature shutdown
occurs, the unit will not restart.
[24] ENA default
Automatic restart when over temperature is
enabled. If an over -temperature shutdown
occurs,
the unit will restart when the temperature
drops.
25
Alarm enable
[25] DIS
Alarm is disabled
[25] ENA default Alarm is enabled
26
Beeps while
primary
source is
interrupted
[26] DIS
Alarm beep is disabled when the status of the
main input source changes
[26] ENA default
Alarm beep is enabled when the status of the
main input source changes
27
Bypass output
when over
load
[27] DIS
Automatic switchover to mains
on overload is disabled.
[27] ENA default
Automatic switchover to mains
on overload is enabled.
28
Max AC
charger
current
[28] 80A default
Max AC charger current. Setting range:
0~ 80A;
29
Split Phase
[29] DIS default
Supply for industrial frequency transformer
(disabled)
[29] ENA
Supply for industrial frequency transformer
(enabled)
35
Battery
undervoltage
recovery
point
[35] 27V default
After a low voltage shutdown the unit will restart
after the battery voltage reaches this setpoint.
36
Max PV
charger
current
[36] 60A default
Max PV charger current. Setting range: 0~ 60A