MCAC-VTSM-2016-04
R410A DC Inverter VRF V4 Plus W Series 50Hz
Specification & Performance 27
5.6 Electric specifications of main units
Model
Main unit
Power Supply
Compressor
OFM
Hz
Voltage
Min.
Max.
MCA
TOCA
MFA
MSC
RLA
KW
FLA
MDVS-252(8)W/DRN1
50
380-415
342
456
18.6
21
20
-
8.7
/
/
MDVS-280(10)W/DRN1
50
380-415
342
456
18.6
21
20
-
9.3
/
/
MDVS-335(12)W/ DRN1
50
380-415
342
456
20.9
21
25
-
12.1
/
/
Remark:
MCA:
Min. Current Amps. (A)
TOCA:
Total Over-current Amps. (A)
MFA:
Max. Fuse Amps. (A)
MSC:
Max. Starting Amps. (A)
RLA:
Rated Locked Amps. (A)
OFM:
Outdoor Fan Motor
kW:
Rated Motor Output (KW)
FLA:
Full Load Amps. (A)
Notes:
1. The current value of combination unit is the total value of each basic model.
2. RLA is based on the following conditions, Indoor temp. 27°C DB/19°C WB, Outdoor temp. 35°C DB
3. TOCA means the total value of each OC set.
4. MSC means the Max. current during the starting of compressor.
5. Voltage range units are suitable for use on electrical systems where voltage supplied to unit terminals is not
below or above listed range limits.
6. Maximum allowable voltage variation between phase is 2%.
7. Selection wire size based on the value of MCA.
8. MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth circuit breaker).