R410A DC Inverter VRF V4 Plus W Series 50Hz
MCAC-VTSM-2016-04
210 Troubleshooting
3.11 P2/H5: Low pressure protection
When the pressure is lower than 0.05MPa, the system will display P2 protection, the ODU in standby. When
the pressure is higher than 0.15MPa, P2 disappears and resumes normal operation.
H5 error will display when system appear 3 times P2 protection in 60 minutes, it cannot resume automatically,
and it can resume only by restarting the machine.
Note:
1. The phenomenon of lack of refrigerant
①
:
Top temperature and discharge temperature of all compressors are higher than normal value, discharge pressure and suction
pressure are both lower than normal value, current is lower than normal value, suction pipe may be frosting. All the phenomenon
will disappear after recharging refrigerant.
2. The phenomenon of the low pressure side is blocked
②
:
The discharge temperature is higher than normal value*, low pressure is lower than normal value*, current is lower than normal
value* and suction pipe may be frosting.
*The normal system running parameters please refer to attached table 3.
*If the system install three-phase protector, and the three-phase protector connect with high pressure switch in series connection,
the system will display P1 protection when fist power on, and P1 protection will disappear after system is steady.
*If the system install three-phase protector, and the three-phase protector connect with low pressure switch in series connection,
the system will display P2 protection when fist power on, and P2 protection will disappear after system is steady.
P2/H5: Low pressure protection
System is lack of refrigerant
①
.
(Refrigerant recharging is not
according to the requirement,
or there has refrigerant
leakage)
Add refrigerant or check up
the leakage of the system
The low pressure side is blocked
②
for squashed pipe, closed EXV,
closed stop valve, dirty filter, etc.
Make sure all valves are open, clean
the filter, if the filter is blocked by ice,
the system should be clean
Yes
Yes
The heat exchange of evaporator
is not good. It may be caused by
dirty heat exchanger, abnormal
IDU fan running, some barrier in
front of the air outlet, etc.
Check the system and
fixed up the error
Yes
No
No
No
Outdoor main PCB
is damaged
Replace the outdoor
main PCB