Midea R22 T1 side-discharge duct manual                                                                                        MCAC-RTSM-201301-01 

32 

 

 

Symptom 

Possible causes 

Way of handing 

The cooling effect is 

poor. 

The condenser or evaporator is 

too dirty. 

Clean the heat-exchanger. 

The filter is blocked. 

Clean the filter. 

The intake orifice or exhaust 

orifice of the indoor and outdoor 

unit is blocked. 

Remove foreign mattes to keep well 

ventilated. 

The door or window is opened. 

Close all the windows and doors. 

Directly exposed to sunlight. 

Obstruct sunlight by curtains or 

jalousie. 

Too many heat sources. 

Reduce heat sources. 

Too high outdoor environment 

temperature. 

It is normal, and the cooling effect of the 

air conditioner is deteriorated. 

The refrigerant is leaked or the 

replenishment is deficient. 

Detect leak, and fill the refrigerant of a 

correct quantity. 

 

Symptom 

Possible causes 

Way of handing 

The cooling effect is 

poor. 

The refrigerant is excessive or 

deficient. 

Detect leak, and fill the refrigerant of a 

correct quantity. 

Air or non-condensable gas 

exists in the refrigerant loop. 

Make a vacuum again and fill the 

refrigerant. 

The compressor fails. 

Repair or replace the compressor. 

The voltage is too high or too 

low. 

Install a voltage regulator. 

The refrigerant loop is 

obstructed. 

Locate the causes and replace the part. 

 

4.3 Faults of remote controller and cause 

  The shift function cannot be set. 

Symptom 

Check item 

Cause 

The wind speed 

cannot be shifted. 

Check whether the mode 

marked the screen of controller 

is 

AUTO

When the auto mode is selected, the 

indoor fan speed will be in automatically 

running and cannot be adjusted. 

Check whether the mode 

marked on the controller screen 

is 

DRY

When the dry mode is selected, the 

indoor unit will set fan speed 

automatically. The speed can 

selectable only in cooling, heating and 

fan mode. 

           

 

 

Содержание MONB-76C

Страница 1: ...r Unit Duct Indoor Unit Technical Manual Applicable Model Indoor unit Outdoor unit MTA1 76HR MONB 76H MTA1 76CR MONB 76C MTA1 96HR MONB 96H MTA1 96CR MONB 96C Midea reserves the right to discontinue o...

Страница 2: ...NS 8 2 5 DIMENSION UNIT MM 10 2 6 SERVICE SPACE 11 2 7 WIRING DIAGRAM 11 2 8 CAPACITY TABLES 13 2 9 ELECTRIC CHARACTERISTICS 11 2 10 SOUND LEVELS 12 2 11 STATIC PRESSURE CURVE 13 3 INSTALLATION 14 3 1...

Страница 3: ...5 MAINTENANCE 41 6 EXPLODED VIEW 44 7 ACCESSORIES 60 8 WIRELESS REMOTE CONTROLLER R51 E STANDARD 60 8 1 REMOTE CONTROLLER SPECIFICATIONS 60 8 2 INTRODUCTION OF FUNCTION BUTTONS ON THE REMOTE CONTROLLE...

Страница 4: ...80 415V 3Ph 50Hz Cooling only 8HP Indoor MTA1 76CR 1 366 450 716 220 240V 50Hz 1Ph Outdoor MONB 76C 1 120 1 558 400 380 415V 3Ph 50Hz Cooling and heating 10HP Indoor MTA1 96HR 1 366 450 716 220 240V 5...

Страница 5: ...Midea R22 T1 side discharge duct manual MCAC RTSM 201301 01 4 1 3 Nomenclature Indoor unit Outdoor unit...

Страница 6: ...tion is not hindered by the location of lighting fixtures or room structure Air inlet and outlet flanges are standard and easy for duct connection Multi diffusers from one indoor unit supply airflow t...

Страница 7: ...ing two speed levels High Pressure Switch When the discharge pressure of compressor is up to 3 3MPa or higher the protection switch will be triggered and if the discharge pressure is down to 2 4MPa th...

Страница 8: ...MCAC RTSM 201301 01 Midea R22 T1 side discharge duct manual 7 2 3 Unit structure...

Страница 9: ...Hydrophilic aluminum fin Hydrophilic aluminum fin Pipe type size Inner grooved copper pipe 7mm Coil W H mm 1 202 378 1 202 378 1 202 378 1 202 378 Number of circuits 8 7 8 7 5 4 5 4 Indoor air flow m...

Страница 10: ...s 1 6 1 6 2 2 Tube pitch row pitch mm 21 13 37 21 13 37 21 13 37 21 13 37 Fin spacing mm 1 5 1 5 1 5 1 5 Fin type Hydrophilic aluminum fin Hydrophilic aluminum fin Pipe size and type mm 7 7 7 7 Inner...

Страница 11: ...Midea R22 T1 side discharge duct manual MCAC RTSM 201301 01 10 2 5 Dimension Unit mm Indoor unit...

Страница 12: ...MCAC RTSM 201301 01 Midea R22 T1 side discharge duct manual 11 Outdoor unit 2 6 Service space Indoor unit...

Страница 13: ...Midea R22 T1 side discharge duct manual MCAC RTSM 201301 01 12 Outdoor unit Top view of the outdoor unit single unit installed Top view of the outdoor unit multiple units installed...

Страница 14: ...Midea R22 T1 side discharge duct manual MCAC UTSM 201301 01 11 2 7 Wiring diagram MTA1 76HR MTA1 96HR...

Страница 15: ...Midea R22 T1 side discharge duct manual MCAC RTSM 201301 01 12 MTA1 76CR MTA1 96CR...

Страница 16: ...Midea R22 T1 side discharge duct manual MCAC UTSM 201301 01 11 MONB 76H MONB 96H...

Страница 17: ...Midea R22 T1 side discharge duct manual MCAC RTSM 201301 01 12 MONB 76C MONB 96C...

Страница 18: ...7 3 14 4 6 4 18 1 15 1 6 7 19 0 15 9 7 1 20 0 16 7 7 4 21 0 17 5 7 8 32 20 17 1 15 6 6 3 18 0 16 3 6 7 18 9 17 2 7 0 19 8 18 0 7 3 20 8 18 9 7 7 21 8 19 9 8 1 2650 23 90 17 8 11 9 6 6 18 7 12 5 6 9 19...

Страница 19: ...18 9 15 8 11 0 32 20 15 4 14 0 9 0 16 2 14 7 9 4 17 0 15 5 9 9 17 9 16 2 10 4 18 8 17 1 10 9 19 7 17 9 11 5 2650 23 90 16 1 10 7 9 3 16 9 11 2 9 8 17 7 11 8 10 3 18 6 12 4 10 8 19 5 13 0 11 3 20 5 13...

Страница 20: ...8 4 23 8 19 8 8 8 25 0 20 8 9 3 26 2 21 9 9 7 32 20 21 4 19 4 7 9 22 4 20 4 8 3 23 6 21 4 8 7 24 7 22 5 9 2 26 0 23 6 9 6 27 3 24 8 10 1 3000 23 90 22 2 14 8 8 2 23 3 15 6 8 6 24 5 16 3 9 1 25 7 17 2...

Страница 21: ...1 6 18 0 13 0 22 7 18 9 13 6 23 8 19 8 14 3 32 20 19 4 17 6 11 6 20 4 18 5 12 2 21 4 19 4 12 8 22 5 20 4 13 5 23 6 21 4 14 1 24 8 22 5 14 9 3000 23 90 20 2 13 4 12 1 21 2 14 1 12 7 22 2 14 8 13 3 23 4...

Страница 22: ...Motor Rated Output kW FLA Full Load Amps A IFM Indor Fan Motor Model Outdoor Unit Power Supply Compressor OFM Hz Voltage Min Max MCA TOCA MFA MSC RLA kW FLA MONB 76H 50 380 415 342 440 15 5 19 3 23 2...

Страница 23: ...1 01 12 2 10 Sound levels Indoor units Model Noise level MTA1 76HR 55 dB A MTA1 76CR 55 dB A MTA1 96HR 55 dB A MTA1 96CR 55 dB A Outdoor units As the following picture the nominal noise level is the m...

Страница 24: ...MCAC RTSM 201301 01 Midea R22 T1 side discharge duct manual 13 Model Noise level MONB 76H 60 dB A MONB 76C 60 dB A MONB 96H 60 dB A MONB 96H 60 dB A 2 11 Static pressure curve MTA1 76...

Страница 25: ...01 14 MTA1 96 3 Installation 3 1 Installating indoor units As the following picture when install the indoor unit select the enough solid and level site with enough space for installation and maintanc...

Страница 26: ...the pendant bolts firmly and reliably in light of the specifice situsation The pendant bolt hole figure is as following picture When the pandant bolt is fixed in wooden structure please put rectangla...

Страница 27: ...rs Int order to prevent air flow shoting do not set the air inlet orifice near the air outlet orifice Install a filter at an easy to maintain place such as intake pipe If without the filter the duct w...

Страница 28: ...e duct manual 17 View of top side View of air inlet side All pipelines must be connected closely and soundly without leak of air The pipelines must be adiabatic and free from condensation The key poin...

Страница 29: ...door unit If miscellaneous articles are piled around the outdoor unit such articles must be 400mm below the top of outdoor unit Top view of the outdoor unit single unit installed Top view of the outdo...

Страница 30: ...n bolt is shown in following figure Snow protection facilities must be installed in the snowfall areas If the snow protection facilities are incomplete faults may occur In order to prevent influence c...

Страница 31: ...as side mm Liquid side mm MONB 76H 9 52 19 0 MONB 76C 9 52 19 0 MONB 96H 9 52 19 0 MONB 96C 9 52 19 0 Allowed length of refrigerant pipe and height difference Allowed value Max Actual length of pipe 5...

Страница 32: ...or unit liquid pipe joint of system A and B at the same time it must be fixed horizontally In the process of installing the connective pipe do not let the air dust water or foreign substance intrude i...

Страница 33: ...eplenish compressed niltrogen to perform airtight test The test is performed by using the compressed niltrogen 2 94MPa 30kg cm2 g Tighten the spool of the gas valve and liquid valve before compressing...

Страница 34: ...square head cover of valves A and B completely Use refrigerant tank to expel air Screw up the pipe nuts at A B C and D completely Loosen and remove the square head cover and the maintenance orifice nu...

Страница 35: ...extracting air for over 15 minutes and check whether the multimeter points at 1 0 10Pa 76cmHg Loosen and remove the square head cover of valves A and B After opening valves A and B completely tighten...

Страница 36: ...ble to retention of the refrigerant In case frequent ventilation is impossible please install the leakage detection alarm device linked with the mechanical ventilation device Use heat resistant materi...

Страница 37: ...0mm or thicker adiabatic wool 16 20kg m2 to the refrigerant pipe and the drain pipe in addition to apply the general heat insulation materials Enough heat insulation materials should also be applied t...

Страница 38: ...stipulated power supply specifications No joint of wires is allowed Indoor units Outdoor units Power 220 240V 50Hz 1Ph 380 415V 50Hz 3Ph Switch capacity of the main power supply fuse A 15 10 40 32 Si...

Страница 39: ...Cooling only units electric wire diagram Pay attention to the phase sequence of the power supply If the phase sequence is reversed the compressor will not start Meanwhile the indicator of outdoor ele...

Страница 40: ...ust be installed in a location suitable for transmitting the signals of the remote controller to the indoor unit Use the remote controller or wired controller to let the unit run in the cooling mode I...

Страница 41: ...l be distributed unevenly In the case the interior of the indoor unit must be cleaned The cleaning units must be performed by professional maintainers This phenomenon may also occur when the air condi...

Страница 42: ...oreign substance or moist enters the air conditioner or other exceptions occur If the air conditioner fails but does not meet the foregoing phenomena obviously check the system in the following proced...

Страница 43: ...Symptom Possible causes Way of handing The cooling effect is poor The refrigerant is excessive or deficient Detect leak and fill the refrigerant of a correct quantity Air or non condensable gas exist...

Страница 44: ...ay disappears Check whether the time set on the time has expired When it comes to the set time of starting operation of the air conditioner the air conditioner will start running automatically and the...

Страница 45: ...Timer lamp flashing at 5Hz T1 room temperature sensor fault of open circuit short circuit Operation lamp flashing at 5Hz T2 pipe temperature sensor fault of open circuit short circuit Defrosting lamp...

Страница 46: ...ration lamp flashing at 5Hz Defrosting lamp flashing at 5Hz For these series products if the condenser temperature sensor malfunction is displayed it is enough to check whether wiring has problem If t...

Страница 47: ...hour 3 System low pressure protection 4 Auto reset after eliminate error Manual reset 3 times protect within 1 hour 4 Current overload protection 6 Auto reset after eliminate error 6 Note Continuously...

Страница 48: ...MCAC RTSM 201301 01 Midea R22 T1 side discharge duct manual 37 Ambient temperature sensor error Condenser temperature sensor error High temperature protection of condenser...

Страница 49: ...Midea R22 T1 side discharge duct manual MCAC RTSM 201301 01 38 System high pressure protection...

Страница 50: ...MCAC RTSM 201301 01 Midea R22 T1 side discharge duct manual 39 Discharge temperature protection...

Страница 51: ...Midea R22 T1 side discharge duct manual MCAC RTSM 201301 01 40 System low pressure protection Current overload protection...

Страница 52: ...Operation required before leaving the unit idle for a long period Let the air conditioner run in the fan mode for about half a day and let its interior be fully dry Switch off the power by the button...

Страница 53: ...duct and move away Move away 4 pieces of M8 screws from the front board of air conditioner Support the bottom of the fan motor assembly by hand and then push it up It needs two persons to do When the...

Страница 54: ...ssembly to make the pin through the hole One person supports the bottom of fan motor assembly another one fixes the M8 screws to make the fan motor assembly fixed on the front board Connect the wires...

Страница 55: ...Midea R22 T1 side discharge duct manual MCAC RTSM 201301 01 44 6 Exploded view MTA1 76HR...

Страница 56: ...201270900011 8 Right cover ass y 1 201270900031 19 Drainage pan ass y 1 201270900024 9 Fan mounting plate ass y 2 201270900018 20 Evaporator left seal plate ass y 1 201270900014 10 Front panel ass y 1...

Страница 57: ...Midea R22 T1 side discharge duct manual MCAC RTSM 201301 01 46 MONB 76H...

Страница 58: ...2300850045 14 Compressor 2 201400400900 4 3 Power transformer 1 202300930238 16 Bottom panel ass y 1 201295100613 4 4 E box 1 201248900037 17 Outlet grille 2 201148700017 4 5 Wire joint 1 202301450130...

Страница 59: ...Midea R22 T1 side discharge duct manual MCAC RTSM 201301 01 48 MTA1 96HR...

Страница 60: ...t cover ass y 1 201270900031 19 Drainage pan ass y 1 201270900024 9 Fan mounting plate ass y 2 201270900018 20 Evaporator left seal plate ass y 1 201270900014 10 Front panel ass y 1 201270900034 21 Ev...

Страница 61: ...Midea R22 T1 side discharge duct manual MCAC RTSM 201301 01 50 MONB 96H...

Страница 62: ...0017 4 4 E box 1 201248900037 18 Motor bracket ass y 1 201295100580 4 5 Wire joint 1 202301450130 19 Front panel 1 201243900048 4 6 Wire joint 1 202301450133 20 Rear vertical panel 1 201248900016 4 7...

Страница 63: ...Midea R22 T1 side discharge duct manual MCAC RTSM 201301 01 52 MTA1 76CR...

Страница 64: ...201270900011 8 Right cover ass y 1 201270900031 19 Drainage pan ass y 1 201270900024 9 Fan mounting plate ass y 2 201270900018 20 Evaporator left seal plate ass y 1 201270900014 10 Front panel ass y 1...

Страница 65: ...Midea R22 T1 side discharge duct manual MCAC RTSM 201301 01 54 MONB 76C...

Страница 66: ...scharge pipe ass y II 1 201675990431 4 4 E box 1 201248900037 18 Discharge pipe ass y I 1 201675990434 4 5 Wire joint 1 202301450130 19 Compressor 2 201400400900 4 6 Wire joint 1 202301450133 20 Brack...

Страница 67: ...Midea R22 T1 side discharge duct manual MCAC RTSM 201301 01 56 MTA1 96CR...

Страница 68: ...270900011 8 Right cover ass y 1 201270900031 19 Drainage pan ass y 1 201270900024 9 Fan mounting plate ass y 2 201270900018 20 Evaporator left seal plate ass y 1 201270900014 10 Front panel ass y 1 20...

Страница 69: ...Midea R22 T1 side discharge duct manual MCAC RTSM 201301 01 58 MONB 96C...

Страница 70: ...ipe ass y II 1 201675990431 4 4 E box 1 201248900037 18 Discharge pipe ass y I 1 201675990434 4 5 Wire joint 1 202301450130 19 Compressor 2 201400400880 4 6 Wire joint 1 202301450133 20 Bracket ass y...

Страница 71: ...cover 1 Install receiving box subassembly Receiving installing box 1 Install receiving box subassembly Installing spring 1 Install receiving box subassembly Installation chart 1 Install receiving box...

Страница 72: ...a mode is selected in a sequence that goes from AUTO COOL DRY HEAT and FAN as the following figure indicates SWING Button Push this switch button to change the louver angle RESET Button When the RESET...

Страница 73: ...r to adjust the TIMER in a clockwise direction VENT Button Push this button to set the ventilating mode The ventilating mode will operate in the following sequence Notes Ventilation function is availa...

Страница 74: ...own on the display panel 8 4 Operating the remote controller 1 Install Replace Batteries The Remote Controller uses two alkaline dry batteries R03 Ir03X2 To install batteries slide back the cover of t...

Страница 75: ...y sensing the difference between the actual ambient room temperature and the set temperature on the remote controller 2 If the AUTO mode is not comfortable for you the desired mode can be selected man...

Страница 76: ...RT time After setting the TIMER there will be a one half second delay before the remote controller transmits the signal to the Air Conditioner Then after approximately another 2 seconds the set temper...

Страница 77: ...set the time you want to stop the operation After setting the TIMER there will be a one half second delay before the remote controller transmits the signal to the Air Conditioner Then after approximat...

Страница 78: ...ons Model KJR 10B DB T E Power Supply Voltage 5 0V DC Ambient Temperature Range 15 C 43 C Ambient Humidity Range RH40 RH90 Performance Features 1 Operating mode Cool heat dry fan and auto 2 Set the mo...

Страница 79: ...rs When the setting time is over 10 hours each time push the button the time moves forward by 1 hour If want to cancel the timer off then adjust the time of timer off as 0 0 CLOCK button Normally disp...

Страница 80: ...f press and hold on it will increase at 1 degree per 0 5 second TEMP button Set indoor temperature down If press and hold on it will decrease at 1 degree per 0 5 second SWING button Push this button f...

Страница 81: ...y When the calculated operating time reaches the setting filter cleaning time the filter cleaning icon will be lighted up to remind the user to clean the filter screen After cleaning filter the user c...

Страница 82: ...es The ECONOMICAL button is available at the auto operation mode 2 COOL HEAT FAN ONLY Operation Push the MODE button to select any one of COOL DRY HEAT or FAN ONLY mode Select the desired temperature...

Страница 83: ...enters into the setting of timer off Push button TIME OFF again and then adjust the time of timer off as desired Continuously push the button the time of timer will increase 0 5 hours per time After t...

Страница 84: ...in following list cannot meet the user s request the user can select the function for setting follow the below method First code Y First code function Second code X 0 1 2 3 4 0 Cooling only Cooling a...

Страница 85: ...Under this interface it will not respond any key operation 11 Indoor unit address setting and query Long press the LOCK key for 5 seconds enter into the indoor unit address setting interface After en...

Страница 86: ...uit of wired controller is low voltage circuit Never connect it with a standard 220V 380V circuit or put it into a same wiring tube with the circuit The shield cable must be connected stable to the gr...

Страница 87: ...joint extrudes out of the wired controller back cover Adjust the bottom of the wired controller board to the wired controller back cover which should be fixed first then press the other end of the wi...

Отзывы: