9.3.9 High temperature protection of compressor top diagnosis and solution(P2)
Check if the air flow system
of indoor and outdoor units
are obstructed?
Clear up the air inlet and outlet or the heat
exchanger of indoor and outdoor units.
Yes
No
Yes
Yes
Turn off the power supply and turn
it on 10 minutes later.
Check if the unit can
start normally.
No
Check if the refrigerant
charge volume is normal?
Recharge the correct
refrigerant volume.
Refrigerant system is blocked, such
as capillary or welded point of pipes.
Yes
Check if all the connection, especially
the connection of OLP (Over Load
Protector) sensor is good.
Correct the connection.
No
Measure the resistance
between the two ports of
the OLP. Is it zero?
Yes
Replace the OLP.
No
Replace the outdoor control PCB.
Yes
No
Содержание MOC-09CFN1-BS0W
Страница 1: ...9ASUL A1 1211 SERVICE MANUAL MIDEA AIRCONDITIONER DC INVERTER SPLIT WALL MOUNTED TYPE...
Страница 17: ...15 MS9A 18HRDN1 MP0W MS9A 18CRDN1 MS0W MS9A 18HRDN1 MS0W MS9A 24HRDN1 MP0W...
Страница 18: ...16 MS9A 09HRDN1 BQ0W MS9A 12HRDN1 BS0W B...
Страница 19: ...17 MS9A 24CRDN1 MP0W...
Страница 20: ...18 MS9A 24HRDN1 MS0W...
Страница 22: ...20 MOC 12CRDN1 MS0W MOC 12HRFN1 MS0W...
Страница 23: ...21 MOF 18HDN1 MP0W MOF 18CRFN1 MS0W...
Страница 24: ...22 MOF 18HRFN1 MS0W MOG 24HDN1 MP0W...
Страница 25: ...23 MOC 09HFN1 BQ0W MOC 12HFN1 BS0W MOF 24HDN1 MP0W...
Страница 26: ...24 MOG 24HDN1 MS0W MOF 24CDN1 MP0W...
Страница 38: ...36 Use torque wrench to tighten the service port cap to a torque of 18N m Be sure to check for gas leakage...
Страница 58: ...56 E4 Reserved function...
Страница 72: ...70...