8.3.6 Indoor fan delayed open function
When the unit starts up, the louver will be active immediately and the indoor fan will open 10s later.
If the unit runs in heating mode, the indoor fan will be also controlled by anti-cold wind function.
8.3.7 Compressor preheating functions
Preheating permitting condition:
If T4(outdoor ambient temperature)
<
3
℃
and the machine connects to power supply newly or if T4
<
3
℃
and compressor has stopped for over 3 hours, the compressor heating cable will work.
Preheating mode:
A weak current flow through the coil of compressor from the wiring terminal of the compressor, then the
compressor is heated without operation.
Preheating release condition:
If T4
>
5
℃
or the compressor starts running, the preheating function will stop.
8.3.8 Zero crossing detection error protection
If AC detects time interval is not correct for continuous 240s, the unit will stop and the LED will display
the failure. The correct zero crossing signal time interval should be between 6-13ms.
8.4 Operation Modes and Functions
8.4.1 Fan mode
(1) Outdoor fan and compressor stop.
(2) Temperature setting function is disabled, and no setting temperature is displayed.
(3) Indoor fan can be set to high/med/low/auto.
(4) The louver operates same as in cooling mode.
(5) Auto fan:
27.5
27
High
Low
25
Medium
25.5
Содержание MOC-09CFN1-BS0W
Страница 1: ...9ASUL A1 1211 SERVICE MANUAL MIDEA AIRCONDITIONER DC INVERTER SPLIT WALL MOUNTED TYPE...
Страница 17: ...15 MS9A 18HRDN1 MP0W MS9A 18CRDN1 MS0W MS9A 18HRDN1 MS0W MS9A 24HRDN1 MP0W...
Страница 18: ...16 MS9A 09HRDN1 BQ0W MS9A 12HRDN1 BS0W B...
Страница 19: ...17 MS9A 24CRDN1 MP0W...
Страница 20: ...18 MS9A 24HRDN1 MS0W...
Страница 22: ...20 MOC 12CRDN1 MS0W MOC 12HRFN1 MS0W...
Страница 23: ...21 MOF 18HDN1 MP0W MOF 18CRFN1 MS0W...
Страница 24: ...22 MOF 18HRFN1 MS0W MOG 24HDN1 MP0W...
Страница 25: ...23 MOC 09HFN1 BQ0W MOC 12HFN1 BS0W MOF 24HDN1 MP0W...
Страница 26: ...24 MOG 24HDN1 MS0W MOF 24CDN1 MP0W...
Страница 38: ...36 Use torque wrench to tighten the service port cap to a torque of 18N m Be sure to check for gas leakage...
Страница 58: ...56 E4 Reserved function...
Страница 72: ...70...