51
-
1<ΔT≤1
℃
Fan-only
ΔT≤-1
℃
Heating
Indoor fan will run at auto fan of the relevant mode.
The louver operates same as in relevant mode.
If the machine switches mode between heating and cooling, the compressor will keep stopping for 15
minutes and then choose mode according to T1-Ts.
If the setting temperature is modified, the machine will choose running function again.
8.4.5 Drying mode
8.4.5.1 Indoor
fan speed is fixed at breeze and can’t be changed. The louver angle is the same as
in cooling mode.
8.4.5.2 Compressor running rules
2.0
1.5
1.0
F3
F2
F1
F1
2.5
0.5
0.0
8.4.5.3 Low indoor room temperature protection
In drying mode, if room temperature is lower than 10
℃
, the compressor will stop and not resume until
room temperature exceeds 12
℃
.
8.4.5.4 Evaporator anti-freezing protection, condenser high temperature protection and outdoor unit
frequency limit are active and the same as that in cooling mode.
8.4.5.5 The outdoor fan operates the same as in cooling mode.
8.4.6 Forced operation function
8.4.6.1 Enter forced operation function:
When the machine is off, pressing the touch button will carry the machine to forced auto mode. After
this, pressing the button once again within 5 seconds, the machine will turn into forced cooling mode.
In forced auto, forced cooling or any other operation mode, pressing touch button will turn off the
Содержание MOC-09CFN1-BS0W
Страница 1: ...9ASUL A1 1211 SERVICE MANUAL MIDEA AIRCONDITIONER DC INVERTER SPLIT WALL MOUNTED TYPE...
Страница 17: ...15 MS9A 18HRDN1 MP0W MS9A 18CRDN1 MS0W MS9A 18HRDN1 MS0W MS9A 24HRDN1 MP0W...
Страница 18: ...16 MS9A 09HRDN1 BQ0W MS9A 12HRDN1 BS0W B...
Страница 19: ...17 MS9A 24CRDN1 MP0W...
Страница 20: ...18 MS9A 24HRDN1 MS0W...
Страница 22: ...20 MOC 12CRDN1 MS0W MOC 12HRFN1 MS0W...
Страница 23: ...21 MOF 18HDN1 MP0W MOF 18CRFN1 MS0W...
Страница 24: ...22 MOF 18HRFN1 MS0W MOG 24HDN1 MP0W...
Страница 25: ...23 MOC 09HFN1 BQ0W MOC 12HFN1 BS0W MOF 24HDN1 MP0W...
Страница 26: ...24 MOG 24HDN1 MS0W MOF 24CDN1 MP0W...
Страница 38: ...36 Use torque wrench to tighten the service port cap to a torque of 18N m Be sure to check for gas leakage...
Страница 58: ...56 E4 Reserved function...
Страница 72: ...70...